RD4 CANopen®
1003 Pre-defined Error Field
This object contains the list of the five previous errors which generated an EMCY
emergency message.
00
Number of current errors [Unsigned8, rw]
Enter 00h to delete the errors list.
01
Last error occurred [Unsigned32, ro]
02…05
Previous errors occurred [Unsigned32, ro]
1005-00 COB-ID SYNC messages
[Unsigned32, rw]
Default = 0000 0080h
1008-00 Device name
[String, const]
It shows the name of the device.
Default = “RD4”
1009-00 Hardware Version
[String, const]
It shows the hardware version of the device.
100A-00 Software Version
[String, const]
It shows the software version of the device.
100C-00 Guard Time
[Unsigned16, rw]
It contains the “node guard time” value expressed in msec (milliseconds). The
Master polls each Slave at regular time intervals issuing RTR messages. This
time-interval is called the “node guard time” and may be different for each
Slave. For further details see section “8.4 Node guarding protocol” on page 68.
Default = 0
MAN RD4 CB E 1.5
Programming parameters
47 of 72
Содержание RD4
Страница 1: ...User s guide RD4 Position measurement control ...
Страница 71: ...This page intentionally left blank ...