LD220
4.6 Analogue output (-AVI- order code)
Analogue output technical specifications
Configuration:
Voltage output (0):
Current output (1):
Current output (2):
Resolution:
Accuracy:
Reaction time:
Current or voltage operation
-10 V … +10 V (Low: 0 … 3 V, High 9 … 30 V)
0 … 20 mA (burden: max. 270 Ohm)
4 … 20 mA (burden: max. 270 Ohm)
16 bits
±0.1%
< 150 ms
A 16 bit analogue output is available through terminal blocks 13 and 14 / 15.
It can be configured and scaled in the
Analog
menu, see the “6.12 Analog
The following configurations are available (see the
on page 74):
0
Voltage output:
-10 V … +10 V
1
Current output:
0 … 20 mA
2
Current output:
4 … 20 mA
The analogue output is proportional to the display value and is referenced to
potential AGND.
AGND and GND are internally connected.
WARNING
Voltage and current outputs of the analogue output cannot be operated
simultaneously.