![Lika EMC58 MT Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/lika/emc58-mt/emc58-mt_user-manual_1915943029.webp)
EM58 – HS58 - HM58 MODBUS TCP/IP
4.6 Line Termination
MODBUS TCP/IP network needs no line termination because the line is
terminated automatically; in fact every Slave is able to detect the presence of
the downstream Slaves.
4.7 Diagnostic LEDs (Figure 1)
Five LEDs located in the cap of the encoder (see the Figure 1) are meant to show
visually the operating or fault status of the encoder and the MODBUS interface.
The meaning of each LED is explained in the following tables.
LED
Description
L/A Link/Activity
LED for port 1
P1 (
green
)
It shows the state and the activity of the physical link (port
1 P1).
OFF
Neither link active nor activity
ON
Port 1 P1 link active, no activity.
BLINKING
Activity on port 1 P1.
LED
Description
NS Network
State Error LED
(
green
/
red
)
It shows the current state of the network.
OFF
No IP address detected or fault status.
ON
green
One MODBUS message at least has been received.
FLASHING
green
The encoder is waiting for the first MODBUS message to be
received.
ON
red
IP address conflict detected or FATAL ERROR.
FLASHING
red
Connection timeout, no MODBUS message has been
received within the set timeout time (see the
LED
Description
PWR Power LED
(
green
)
It shows the power supply state.
MAN EM58_HS58_HM58 MT E 1.1.odt
Electrical connections
29 of 104
Содержание EMC58 MT
Страница 101: ...This page intentionally left blank ...
Страница 102: ...This page intentionally left blank ...