AMM80 • SSI, BiSS, & RS-485
7.2.3 Read register
Master Encoder
→
CF
ADF
CRC
Encoder Master
→
CF
ADF
EDF
CRC
7.3 Field detail
7.3.1 Control Field
Control Field CF is related to Data Field DF, for a correct Data ID see the “7.4
Data Field” section on page 46.
Frame type
Data ID
CF value
Data capture
Data ID 0 (singleturn value)
02h
Data ID 1 (multiturn value)
8Ah
Data ID 2 (fixed value = 23h)
92h
Data ID 3
1Ah
Writing the register
Data ID 6
32h
Reading the register
Data ID D
EAh
Resetting data/errors
Data ID 7 (singleturn value)
BAh
Data ID 8 (singleturn value)
C2h
Data ID C (singleturn value)
62h
7.3.2 Status Field
Status Field SF is configured as follows:
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
EE_1
EE_0
EI_3
EI_2
EI_1
EI_0
EI: All Encoder Information bits have fixed value = “0”
EE: Encoder Error bits
EE_0 = “1”
→
→
, or
MAN AMM80 SSI_BiSS_RS485 E 1.5.odt 7 – RS-485 serial interface 45 of 60