LIGHTSAFE ER8M2 Скачать руководство пользователя страница 1

FS.06/11 REV 3 

  

ER8M2 / ER8NM2   Lighting Instructions (Maintained and Non Maintained 8W Bulkhead)  

General Information   

These  instructions  contain  important  information  regarding  safety.  They  should  be  read 
carefully  and  should  be  retained  for  future  reference.  The  company  will  not  accept  any 
responsibility  for  any  injury,  damage  or  loss  which  may  arise  due  to  incorrect  installation, 
operation or maintenance due to non-adherence to these instructions.  

Our products are designed to comply with the recommendations of BS 5266-1: 2005 code of 
practice  for  emergency  lighting  of  premises  and  be  installed  by  competent  person  in 
accordance with the relevant wiring regulations  

Before installation of any type of emergency lighting always seek the advice of the local fire 
prevention officer (or equivalent authority)   

Luminaire information   

Model ER8M2 (Maintained) 

Model ER8NM2 (Non Maintained)   

Rated voltage 240V AC 50Hz    
Lamp type 8W T5 
IP65     
Product size : (LxWxH) 352 x 117 x 76mm 
Battery Type : Ni-Cd  2.4V  4.5Ah 
Recharge time : 24 hours : Initial Charge : 36 hours 
Over Discharge Protection   Yes 
Emergency Operation Time 3 Hrs  

Maintained Version Only - For lamp always on, link Ls (Switched Live) to terminal L 
(Permanent Live).  If  Ls  not connected, fitting works as non maintained.  

 

All self 

 

contained emergency lighting luminaires require a continuous (un-switched) 220V 

 

240V single phase 50hz supply to keep the inbuilt batteries charged.    

Installation of the fitting    

Installation  should  only  be  carried  out  in  accordance  with  the  current  edition  of  the 

Regulations for Electrical Installations  BS 7671 and with the requirements of BS 5266-1    

Do not high voltage insulation test the luminaire as this may damage the control gear    

Before starting the installation ensure that the electricity supply is isolated and that it can not 
be reenergised accidentally.   

1)  Remove the front diffuser from the body by removing the 2 fixing screws  

2)  Release the metal gear tray by easing the plastic clips away from the metal tray and 

lifting the metal tray away from the base   