background image

IS:26600

READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING TRACK

This fixture is intended for installation in accordance with the National Electrical Code and local or Federal code
specifications. To assure full compliance with codes and regulations, check with your local electrical inspector
before installation. To prevent electric shock, turn off electricity at fuse box before proceeding.

Save these instructions for maintenance reference

and refer to them when additions to or changes in the track configuration are made.

INSTRUCTION SHEET NO.

A0397

Page 1 of 4

FALL RIVER, MASSACHUSETTS 02720

MONTREAL, QUEBEC, CANADA

ProSpec™ track lighting is designed to support and energize ProSpec™ Lytespots

®

 which can be

attached anywhere along the track. It is a four conductor system, continuously grounded through-
out, to be supplied by two single 120V, 20 amp, 60Hz branch circuits. It is not intended for use with
a power cord or convenience receptacles. ProSpec™ is listed by Underwriters Laboratories, Inc. It
may only be used with electrical fittings identified for use with ProSpec™ track.

Installation Instructions for ProSpec

 Track Lighting--

Recessed Feed Track and Plain Track Units.

IMPORTANT SAFETY INSTRUCTIONS

Read all Track, Connector, Feed-in Kits, and Accessory Instruction Sheets before
installing any ProSpec

 Track item. When installing or using this track system, basic

safety precautions should be followed:

Read all instructions

 before installing the track system.

Do not install in wet media (concrete, plaster, etc.).

This track system is intended for installation in accordance with the National
Electrical Code and Local or Federal Codes.

Do not install this track in wet or damp locations.

Do not install any part of this track system less than 5 feet above floor.

Do not install any fixture assembly closer than 6 inches from any curtain, or similar
combustible material.

To prevent electrical shock, turn off electricity at fuse box before installing the track
or adding to or changing the configuration of the track.

Instructions for grounding per instruction sheet of the feed-in kit used must be
followed. Failure to do so may result in a hazardous condition.

Use #12 ga. AWG solid wire only (not stranded wire) for supply to track.

Observe polarity, white supply lead (neutral) to contact marked “NEUT” on screw
terminal connectors.

Do not exceed 4 feet between mounting points.

Do not attempt to energize anything other than track lighting fixtures on the track.
To reduce the risk of fire and electrical shock, do not attempt to connect power tools,
extension cords, appliances and the like to the track.

SAVE THESE INSTRUCTIONS

Содержание ProSpec Track Lighting

Страница 1: ...S Read all Track Connector Feed in Kits and Accessory Instruction Sheets before installing any ProSpec Track item When installing or using this track system basic safety precautions should be followed Read all instructions before installing the track system Do not install in wet media concrete plaster etc This track system is intended for installation in accordance with the National Electrical Cod...

Страница 2: ...Clips sold separately Cat 26090 set of 4 Fig C Slide or snap the hanger clips onto the track Assemble the screws and nuts onto the mounting clips Recommended two clips per 4 track three clips per 8 track and four per 12 track Always use more then one clip per track length Additional clips may be added for more support The clips should be evenly spaced along the track length Tighten the clip on the...

Страница 3: ...strip each wire Attach wires to the screw terminals Wires must be tightly held in the screw terminals Neutral wires must be attached to screw terminals marked NEUT Ground wire must be attached to the green ground screw Snap Bottom Cover into the track FIG G A0397 Page 3 of 4 Electrical Connector Knockout FeedTrack Top Plate Bottom Cover FIG E Use 12 ga solid copper wire for feed connections includ...

Страница 4: ...r or by using Plain Track with multiple Power Extensions The Power Extension Connector is sold separately CAT NO 26646WH See instructions with the power extension for installation details NOTE THIS TRACK SYSTEM IS NOT POLARIZED Connectors can be installed into both sides of the Plain Track and in any orientation There is no key that will prevent insertion of the connectors Connectors cannot be att...