background image

LOT Series

5.0-10.0 

K

VA S

INGLE

 P

HASE

 UPS

Page 1 of 2

Job Information 

Type:

Job Name:

Cat. No.:

Notes:

LOT

D

C

Overall Characteristics

Features: 

87% throughput 

efficiency with 85% emergency 

efficiency. Operating 

temperature range 32ºF 

(0ºC) to 104ºF (40ºC). Fault 

current rating of 42 kAIC. 

Audible noise less than 50 dB 

at 3 ft on “A” weighted scale. 

Automatic low battery voltage 

disconnect. Double conversion 

with no interruption. Solid 

state pulse width modulated 

inverter. Internal, make before 

break maintenance by-pass. 

Standard UL 924 compliant, 

90 minute battery back up. 

UL 924 auxiliary equipment 

10 and 20 minute back up 

available. Microprocessor 

control and diagnostic system. 

LED array system status panel. 

Fault annunciating audible 

alarm. Current limiting start 

sequence. Optional output 

circuit breakers (OCB) and 

circuit breakers with trip alarm 

(OCBA). Optional normally 

off load (NOL) energizes only 

during power outage, normally 

off load with time delay (TDT) 

also available. Free standing 

NEMA 1 enclosure. Lockable 

control access panel. Seismic 

anchoring compatible.

Application: 

The solid state 

pulse width modulated (PWM) 

inverter offers enhanced load 

compatibility. It operates 

incandescent, magnetic, and 

electronic ballast fluorescent, 

high power factor compact 

fluorescent and high intensity 

discharge (HID) luminaries. 

Provides conditioned, 

uninterruptible power for 

other types of critical loads. 

Consult factory for non-lighting 

load applications.

Input: 

Input power factor 

correcting to 0.99. Frequency 

range 60 Hz, ±2.5 Hz. Input 

harmonic current distortion 

< 5%THD. UL1449, ANSI/IEEE 

C62.41 surge suppression.

Output: 

Sine wave output. 

Voltage regulation ±2%. 

Frequency regulation is 

synchronized to utility and free 

running 60 Hz, ±0.5%. Output 

voltage distortion maximum 

3% THD with linear load. Load 

power factor capability 0.7 lead 

to 0.7 lag. Overload capability 

125% for 10 seconds.

Code Compliance

UL 924 and UL 924 auxiliary 

equipment listed.

Warranty

Lightolier will provide parts 

and on-site labor for the first 

12 months following start-

up of the product, and parts 

only for an additional 12 

months.  If factory start-up is 

not executed within 120 days 

of shipment, Lightolier will 

provide a parts warranty for 

12 months from the date of 

shipment. Consult factory for 

extended warranty and service 

option.

B

5.0 kVA

36"

24"

80"

N/A

6.0-10.0 kVA

36"

24"

80"

29"

Width (A)

Depth (B)

Height (C)

Width (D)

A

Electronics

Cabinet

Battery

Cabinet

Отзывы: