DC Power System Installation Manual

FlexPower Generation 2

Содержание FlexPower Generation 2

Страница 1: ...LifeSafety Power Inc PH 888 577 2898 TechSupport LifeSafetyPower com P03 40 Rev A18 DC Power System Installation Manual FlexPower Generation 2...

Страница 2: ...stallation Wire Routing 7 1 5 AC Switch and terminal wiring 8 1 6 RS485 Address Switch Settings 8 1 7 Power Up and Basic System Verification Checklist 9 Section 2 Troubleshooting and Maintenance 10 2...

Страница 3: ...i The system and any batteries if used should be tested at least once per year to ensure proper opera tion i Batteries if used should be maintained at an am bient temperature of between 32 and 120 deg...

Страница 4: ...Battery Type Jumper section 1 2 15 AC Earth Ground Jumper section 1 2 6 RS485 Board section 1 2 AC LED Connector section 1 2 7 RS485 Address section 1 2 8 Models ending in E are factory preset for 230...

Страница 5: ...L1076 applications after installation is complete the installer must install the two supplied 1 long screws to the edge of the enclosure s cover for additional security Mounting an FPO PS Board to an...

Страница 6: ...panel 2 1 AC GND FLT AC FLT FAI SYS FLT 2 1 Bat Set Bat Set 2 1 DC2 DC1 REV BAT DC2 DC1 FAI INPUT FAI INPUT SYS FLT SYS FLT AC FLT AC FLT 12V 24V Observe battery polarity or damage may result Observe...

Страница 7: ...for AC voltage out of range indication H Always confirm the absence of AC power with a meter before servicing to prevent electric shock 6 Earth Ground Fault Detection JP2 The EARTH GND DET jumper ena...

Страница 8: ...panel 2 1 AC GND FLT AC FLT FAI SYS FLT 2 1 Bat Set Bat Set 2 1 DC2 DC1 REV BAT DC2 DC1 FAI INPUT FAI INPUT SYS FLT SYS FLT AC FLT AC FLT 12V 24V Observe battery polarity or damage may result Observe...

Страница 9: ...Connections are as follows DC1 This faston provides a constant voltage output for con nection to the accessory boards BR The DC Common DC Ground for the FPO power supply DC2 This faston provides an FA...

Страница 10: ...g of the FAI Input is achieved by placing a NC contact across the two L terminals The FAI may be activated by any of the methods listed FAI Deactivates when the input is deactivated AND the NC Latchin...

Страница 11: ...installation and all wiring methods shall be in accor dance with ANSI NFPA70 and all local codes For ULC S527 compliance installation and all wiring methods shall be in accordance with the Canadian E...

Страница 12: ...f On On On 1 On On On Off 9 Off On On Off 2 On On Off On 10 Off On Off On 3 On On Off Off 11 Off On Off Off 4 On Off On On 12 Off Off On On 5 On Off On Off 13 Off Off On Off 6 On Off Off On 14 Off Off...

Страница 13: ...the DC2 output pow ers down Deactivate the FAI input and reset the input if configured for latching and verify that the red FAI LED extinguishes and the DC2 output returns to normal 8 If the battery...

Страница 14: ...output voltage setting Problem with battery charging circuit Contact LifeSafety Power High or Low Output Voltage Measure the output voltage at the DC1 terminals The voltage should be 12 50V for the 1...

Страница 15: ...ction within the FPO supply Contact Life Safety Power Missing Battery Not Detected Improper setting of BAT DETECT Jumper The BAT DETECT jumper must be ON to detect a missing battery Earth Ground Fault...

Страница 16: ...10A For UL1076 applications FPO250 output current at 24V is derated to 8A max Ripple 120mV 120mV 120mV Regulation 2 2 2 Efficiency 80 120VAC 60Hz In Full Load No Batt 86 120VAC 60Hz In Full Load No Ba...

Страница 17: ...m D Approximate Weight base cabinet 8 lbs 3 5 kg empty Enclosure E2 M V Size 20 H x 16 W x 4 5 D 508mm H x 406mm W x 114mm D Approximate Weight base cabinet 18 lbs 8 0 kg empty Enclosure E5 M Size 8 6...

Страница 18: ...ght zone power control Class 2 replacement board M8 Eight zone managed power control replacement board M8P Eight zone managed power control Class 2 replacement board NL2 NetLink network communication...

Страница 19: ...ation Any UL1076 installation must use the tamper switch to indicate the opening or removal of the front door of the enclosure Below is a certificate required for UL603 installations to be cut out fra...

Страница 20: ...l be monitored by a listed alarm system The following sections cover specific requirements based on application UL1076 Proprietary Burglar Alarm Applications 1 The LifeSafety Model TS 20 tamper switch...

Страница 21: ...17 UL Compliance Verification...

Страница 22: ...ty Power s only obligations are those in the LifeSafety Power Standard Terms and Conditions of Sale for this product and in no case will LifeSafety Power or its distributors be liable for any incident...