background image

69-350DCS

072020

New

 

Auto

 

Dehumidistat

 

Function

prevents unwanted use of the dehumidistat when outdoor temperatures exceed 15°C (59°F).

INSTALLER:

 

Leave

 

this

 

manual

 

for

 

the

 

homeowner

Operation

 

and

 

Installation

 

Manual

Commercial

 

Double

 

Core

 

Heat

 

Recovery

 

System

 

Model

350DCS

Installation and wiring to be in accordance 

with CEC, NEC and local electrical codes. 

Important: Read and save these instructions.

Содержание 350DCS

Страница 1: ...door temperatures exceed 15 C 59 F INSTALLER Leave this manual for the homeowner Operation and Installation Manual Commercial Double Core Heat Recovery System Model 350DCS Installation and wiring to b...

Страница 2: ...lation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment i e a forced air furnace or air handler operating at a higher static...

Страница 3: ...0 WATTS Low speed 187 WATTS High speed 610 Amp rating 6 3 AIRFLOWS Each Air Stream 250 200 150 100 50 0 1 0 2 100 90 80 300 143 400 190 500 235 600 282 AIRFLOW IN CFM L s NOTE Exhaust Relative Humidit...

Страница 4: ...20 minutes ON 40 minutes OFF or 10 minutes ON 50 minutes OFF for even less ventilation Controlling Your HRV Glossary DEFROST MODE to ensure reliable operation during cold weather the HRV will automati...

Страница 5: ...ation and increase to high speed during increased activity levels such as cooking and showering etc II 20 Minutes On 40 Minutes Recirculation 20 hr 40 hr This mode ventilates for 20 minutes and recirc...

Страница 6: ...or 60 minutes and 4 times to disable The will appear on the screen and the corresponding section of the clock will flash to indicate the time interval selected When the timer runs out the unit will re...

Страница 7: ...Humidity Control Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels This feature is only effective when the outdoor temperature is below 59 F 15 C...

Страница 8: ...umidity level is lower than the setting Refer to the unit s Home Owner s manual for instructions on how the Dehumidistat works The Dehumidistat will override the current fan speed setting to high fan...

Страница 9: ...densation on windows indicates a high level of humidity The amount of condensation on the windows will increase as outdoor temperatures drop Your HRV will reduce indoor humidity levels when outdoor ai...

Страница 10: ...is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either...

Страница 11: ...02 control drill a 1 in hole in the center Figure D For BC02 BC03 or BC04 controls cut in a 3 4 in by 1 in oval hole in the wall Figure E or F 7 Pull 3 wire 20 gauge min 100 ft length max through the...

Страница 12: ...Back Plate Figure C 7 Secure a single wire to the Wire Retainer located on the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate...

Страница 13: ...eater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Remov...

Страница 14: ...ss Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan o...

Страница 15: ...h Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Statu...

Страница 16: ...inal Block CAUTION Consideration should be given to competing airflows when connecting the HRV in conjunction with an Air Handler Furnace Blower system Setting Standby when using a Main Control CAUTIO...

Страница 17: ...nnel Supplied by others Vibration Isolators Supplied by others Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines...

Страница 18: ...high quality caulking preferably acoustical sealant and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood A properly designed ducting sy...

Страница 19: ...interfaced with the Airhandler Furnace when this system is used refer to Interlocking the HRV to an Airhandler Furnace blower in this manual The HRV exhaust take off connection must be at least 3 ft...

Страница 20: ...introduced directly into the ceiling space but this should occur near the air handler s intake In installations where it is satisfactory to provide general exhaust from the space the air to be exhaus...

Страница 21: ...t with a zip tie zip tie not included Pour a cup of water into the drain pan of the HRV after the drain connection is complete This creates a water seal that prevents odors from being drawn up the hos...

Страница 22: ...unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation ma...

Страница 23: ...atching the H channel and temporarily preventing its removal In most cases washing the core in a mild detergent and warm water will be all that is needed to completely clean them Do not use harsh chem...

Страница 24: ...Ensure that the pans drain completely and in a reasonable amount of time Note if the water does not drain right away check for blockage in the drain line also check that the drain line has a good slo...

Страница 25: ...Wiring Diagram Model 350DCS 26...

Страница 26: ...n Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt with at t...

Страница 27: ...28 info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 350DCS 072020...