OPERATION AND

INSTALLATION MANUAL

Contains ControlAir 15

For Models:

95MAX
155MAX
155ECM
155MAXRX
200MAX
200MAXRX
MAXTOP
195DCS
300DCS
200ERV
200ERVD

CAUTION

Before installation, careful consideration

must

be given to

how this system will operate if connected to any other piece
of mechanical equipment, i.e. a forced air furnace or air
handler, operating at a higher static. After installation, the
compatibility of the two pieces of equipment

must

be

confirmed by measuring the airflow’s of the Heat Recovery
Ventilator (HRV) Energy Recovery Ventilator (ERV) by
using the balancing procedure found in this manual.

It is always important to assess how the operation of any
HRV/ERV may interact with vented combustion equipment
(ie. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).

NEVER

install a ventilator in a situation where its normal

operation, lack of operation or partial failure may result in
the backdrafting or improper functioning of vented combus-
tion equipment!!!

IMPORTANT - PLEASE READ THIS
MANUAL BEFORE INSTALLING
UNIT.

Содержание 200MAX

Страница 1: ...o any other piece of mechanical equipment i e a forced air furnace or air handler operating at a higher static After installation the compatibility of the two pieces of equipment must be confirmed by measuring the airflow s of the Heat Recovery Ventilator HRV Energy Recovery Ventilator ERV by using the balancing procedure found in this manual It is always important to assess how the operation of a...

Страница 2: ...very Ventilator HRV is designed to pro vide fresh air into a building while exhausting an equal amount of stale air During the winter months the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhaust ed to the outdoors During summer months when the indoor space is air conditioned the Heat Recovery Ventilator will help in cooling the incoming fresh...

Страница 3: ...difier and on its own will not take moisture out of the air So why use an ERV A properly operating air conditioner will not only lower the temperature in your house but will also lower the humidity level This prevents an uncomfortable cold and damp situation In fact about 2 3 of the energy used by the air conditioner system is to remove mois ture Therefore when ventilating in the summer less moist...

Страница 4: ...4 ...

Страница 5: ...nted galvanized steel G60 for superior corrosion resis tance Insulated to prevent exterior condensation Drain connections 2 1 2 12 mm OD CONTROLS ControlAir 15 Standby ON mode 20 ON 40 OFF mode Recirculation mode on compatible units each mode has 5 speeds Control pad can be removed from HRV and remotely mounted WEIGHT 52 lbs 23 6 kg Shipping Weight 56 lbs 25 4 kg OPTIONS 99 104 Digital Electronic ...

Страница 6: ...RS BLOWERS NOTE Front clearance of 25 inches 635 mm is recommended for servicing unit RECIRCULATING DEFROST DAMPER MOTOR CORE OPTIONS 99 104 Digital Electronic Timer 20 40 60 min 99 109 Air Sentry Air Quality Monitor designed to accept remotely mounted Control Pad 99 250 Ventilation Dehumidistat Dehumidistat designed to accept remotely mounted Control Pad 99 163 Duct Heater w Electronic SCR Thermo...

Страница 7: ...for servicing unit RECIRCULATING DEFROST DAMPER MOTOR CORE OPTIONS 99 104 Digital Electronic Timer 20 40 60 min 99 109 Air Sentry Air Quality Monitor designed to accept remotely mounted Control Pad 99 250 Ventilation Dehumidistat Dehumidistat designed to accept remotely mounted Control Pad 99 163 Duct Heater w Electronic SCR Thermostat 1 Kw 6 150 mm 99 164 Duct Heater w Electronic SCR Thermostat 2...

Страница 8: ...ROM OUTSIDE STALE AIR TO OUTSIDE FRESH AIR TO INSIDE CONDENSATE DRAINS FILTERS BLOWERS RECIRCULATING DEFROST DAMPER MOTOR CORE OPTIONS 99 104 Digital Electronic Timer 20 40 60 min 99 109 Air Sentry Air Quality Monitor designed to accept remotely mounted Control Pad 99 250 Ventilation Dehumidistat Dehumidistat designed to accept remotely mounted Control Pad 99 163 Duct Heater w Electronic SCR Therm...

Страница 9: ... 25 C 66 VAC 60HZ 120 WATTS Low speed 87 WATTS High speed 164 Amp rating 1 4 TI 99 NE 0904 200MAX FANCURVE 225 200 175 150 125 100 75 50 25 0 3 0 4 0 5 0 6 0 7 0 8 0 9 Air Flow cfm Static Pressure inH20 1 0 HIGH SPEED MEDIUM HIGH SPEED MEDIUM SPEED MEDIUM LOW SPEED LOW SPEED 4 5 3 2 1 5 4 3 2 1 Manufacturers Data Model 200MAX DIMENSIONS 200MAX inches mm All units conform to CSA and UL standards EN...

Страница 10: ... F 25 C 66 VAC 60HZ 120 WATTS Low speed 87 WATTS High speed 164 Amp rating 1 4 200MAX FANCURVE 225 200 175 150 125 100 75 50 25 0 3 0 4 0 5 0 6 0 7 0 8 0 9 Air Flow cfm Static Pressure inH20 1 0 HIGH SPEED MEDIUM HIGH SPEED MEDIUM SPEED MEDIUM LOW SPEED LOW SPEED 4 5 3 2 1 5 4 3 2 1 Manufacturers Data DIMENSIONS 200MAX RX inches mm All units conform to CSA and UL standards ENGINEERING DATA THERMAL...

Страница 11: ...125 Pa 149 71 Maximum Temperature Recovery 80 Sensible Effectiveness 117 cfm 55 L s CSA C439M 72 Sensible Efficiency 117 cfm 55 L s 32O F 0 C 64 Sensible Efficiency 67 cfm 31 L s 13O F 25 C 70 VAC 60HZ 120 WATTS Low speed 74 WATTS High speed 164 Amp rating 1 4 TOP VIEW SIDE VIEW 25 1 2 648 mm 26 1 2 673 mm 22 1 2 572 mm FRONT VIEW ALL DUCT CONNECTIONS ARE 6 150 mm 18 457 mm 7 1 2 191 mm SUPPLY OF ...

Страница 12: ...able air filters in exhaust and supply air streams MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit DEFROST Damper defrost system DEHUMIDISTAT Adjustable Internal Dehumidistat CASE Twenty gauge prepainted galvanized steel G60 for superior corrosion resis tance Insulated to prevent exterior condensation Dra...

Страница 13: ...filters in exhaust and supply air streams MOUNTING THE HRV Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit DEFROST Damper defrost system DEHUMIDISTAT Adjustable Internal Dehumidistat CASE Twenty gauge prepainted galvanized steel G60 for superior corrosion resis tance Insulated to prevent exterior condensation Drain connec...

Страница 14: ...CE Net supply airflow in cfm L s against external static pressure E S P cfm L s 0 1 25 Pa 232 109 0 2 50 Pa 223 105 0 3 75 Pa 215 102 0 4 100 Pa 195 92 0 5 125 Pa 189 89 Sensible Effectiveness 127 cfm 60 L s CSA C439M 67 Sensible Efficiency 32 F 0O C 60 Total Efficiency 55 VAC 60HZ 120 WATTS Low speed 87 ENGINEERING DATA LATENT RECOVERY MOISTURE TRANSFER CORE The cross flow energy recovery core tr...

Страница 15: ...l static pressure E S P cfm L s 0 1 25 Pa 232 109 0 2 50 Pa 223 105 0 3 75 Pa 215 102 0 4 100 Pa 195 92 0 5 125 Pa 189 89 Sensible Effectiveness 127 cfm 60 L s CSA C439M 67 Sensible Efficiency 32 F 0O C 60 Total Efficiency 55 VAC 60HZ 120 WATTS Low speed 87 ENGINEERING DATA LATENT RECOVERY MOISTURE TRANSFER CORE The cross flow energy recovery core transfers heat and water vapour between the two ai...

Страница 16: ...essor automatically activates the defrost system only as it is needed To be an efficient heat recovery device the HRV ERV must effectively provide for core defrost as well as providing efficient heat exchange As outdoor conditions cool the temperature sensor thermistor tracks the supply air temperature The thermistor then sends its signal to the microprocessor circuit board which initiates only th...

Страница 17: ...RV ERV will operate in recirculate mode at the selected speed Optional remote controls will override unit into high speed ventilate mode To select speed Momentarily press fan selection button and release HRV ERV will move into next speed OFF is indicated by no yellow LED illuminated Speed 1 is the first yellow LED Speed five is indicated by a flashing speed 4 LED Automatic Defrost During cold outd...

Страница 18: ... DEFROST flashing red Fan Select Button Press and release to change speeds Press and hold to change mode of operation Optional Control Wiring Terminals Not available on all models Control Module Control Pad ControlAir All controls wire to matching colour on the Control Module Control Pad can be removed and mounted in a remote location Control Pad mounts in a 2 x 4 box or can be mounted in the opti...

Страница 19: ...at which will provide the user with com plete control over their ventilation system from a convenient location Optional Timers Timers should be present when the HRV ERV is exhausting from speciific locations i e bathrooms laundry rooms The Digital Electronic Timer is the best selection however the crank timer will be necessary if only 2 lead low voltage wires are present Only one main control can ...

Страница 20: ...tween 30 50 The dehumidistat will override the ventilator to high speed when the moisture level in the home exceeds the set point on the control Once the humidity in the house is reduced the HRV ERV will revert back to its previous setting The dehumidistat should be set to off for all seasons except the heating season Note If your HRV ERV is equipped with an internal and an external dehumidistat t...

Страница 21: ...me Simply bend a standard duct fitting to the correct shape and attach to the oval port using the same method as for a round port 95 MAX Air Flow Stale air enters the FRONT RIGHT side port The air will pass down the front half of the core then up the back half of the core and out the RIGHT REAR port Fresh outdoor air will enter the LEFT REAR port and pass down the back half of the core It will the...

Страница 22: ...e polarity of the power line that is switched by the safety disconnect switch The hot line black is the proper line to be switched To confirm the proper polarity use a voltmeter or test lamp to ensure there is no power after the switch when the door is open Check between that point and ground on the cabinet This must be done as dwellings are occasionally wired improperly Always make sure that the ...

Страница 23: ...flexible duct to both the HRV ERV port and the weatherhood prior to clamping To minimize air flow restriction the flexible insulated duct that connects the two outside weatherhoods to the HRV ERV should be stretched tightly and be as short as possible Twisting or folding the duct will severely restrict air flow See below for the recommended connection of flexible insulated ducts to the the outside...

Страница 24: ...100 mm and no more than 12 inches 300 mm from the grille Stale Air Exhaust System The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur It is recommended that return air ducts are installed in the bathroom kitchen and laun dry room Additional return air ducts from strategic locations i e greenhouse atrium swimming pool sauna etc ma...

Страница 25: ...od air distribution 2 Weatherhood arrangement is for drawing purposes only 6 2 m minimum separation required 18 460 mm above grade minimum 3 Due to the differences in pressure between the HRV ERV and the equipment it is being connected to the HRV ERV s airflow must be confirmed on site using the balancing procedure found in the installation manual Return Air 3 min recommended Partially Dedicated S...

Страница 26: ...o run continuously or interlocked with HRV ERV 2 A minimum separation of 40 inches 1 m is required between the two direct connections 3 The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air 4 Weatherhood arrangement is for drawing purposes only Six feet 2 m minimum separation required Eighteen inches 460 mm above grade minimum 5 Due to the d...

Страница 27: ...any fresh air 3 Weatherhood arrangement is for drawing purposes only Six feet 2 m minimum separation required Eighteen inches 460 mm above grade minimum 4 Due to the differences in pressure between the HRV ERV and the equipment it is being connected to the HRV ERV s airflow must be confirmed on site using the balancing procedure found in the installation manual 3 min recommended 3 min recommended ...

Страница 28: ...intended All air movement devices have a performance curve The amount of air CFM that an HRV ERV will deliver is directly related to the total external static pressure E S P of the system Static pressure is a measure of resistance imposed on the blower by length of duct work number of fittings used in duct work duct heater etc Duct configuration may change depending on the model See Specifications...

Страница 29: ...out 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or other manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube coming out of the top of th...

Страница 30: ...no further than 1 2 from outside edge of collar so as not to impede operation of the damper 1 2 Hard Rigid ducting Insulated flexible ducting Installations where the HRV is ducted directly to the return of a furnace may require additional dampening on the fresh air to building duct This is due to the high return static pressures found in some furnace installations Balancing Collar Instructions ...

Страница 31: ...f the cabinet NOTE Core will appear to stick out from cabinet approxi mately 1 8 3mm This is designed this way so that the access door will fit tight against the core 4 Motors Maintenance Free 5 Drain condensate Line Clean once a year Inspect drain line drain spout and P trap for block age mould or kinks Flush with warm soapy water and replace if worn bent or unable to clean 6 Clean Duct Work if R...

Страница 32: ...ll appear to stick out from cabinet approximately 1 8 3 mm This is designed this way so that the access door will fit tight against the core 4 Motors MAINTENANCE FREE 5 Clean Duct Work if Required The duct work running to and from the ERV may accumulate dirt Wipe and vacuum the duct once every year You may wish to contact a Heating Ventilation company to do this 6 General Maintenance Twice a Year ...

Страница 33: ...k supply voltage at house check duct installation increase the speed of the HRV ERV have contractor balance HRV ERV locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant eg over a sofa turn down the HRV ERV supply speed A small duct heater 1kw could be used to temper the supply air placeme...

Страница 34: ...SABLE RECIRCULATION REMOVE SEL2 DRY CONTACT T7 T8 T1 T2 T6 N C COMMON N O T15 MICRO PROCESSOR BOARD DEHUMIDISTAT P2 P5 INTERNAL WARNING 750 ma MAX FUSE 2 1 P6 LINE CHASSIS CONTROLAIR 15 YEL GRN ORN RED BLK Air Handler Furnace Terminal Strip Connecting the HRV ERV as illustrated will ensure the Air Handler Furnace Blower Motor is operating whenever the HRV ERV is ventilating Consideration must be g...

Страница 35: ...ER SOURCES TO UNIT SEE DEFROST DETAIL WARNING 750 ma MAX FUSE FAN MOTOR DETAILS TI 89A NE 1105 2 1 P6 RESIDENTIAL WIRING DIAGRAM LINE PLUG IN CONNECTOR AUTO TRANSFORMER DETAIL 3 2 2 1 1 5 6 4 P5 P6 P5 PIN 1 BLUE PIN 4 RED PIN 2 YELLOW PIN 5 WHITE PIN 3 BROWN PIN 6 BLACK P6 PIN 1 GREEN PIN 2 GREEN AUTO TRANSFORMER Note All control connections are labeled by colour Connect to corresponding colour wi...

Страница 36: ...EL2 FOR R 2000 REMOVE SEL1 TO DISABLE RECIRCULATION REMOVE SEL2 DRY CONTACT T7 T8 T1 T2 T6 N C COMMON N O T15 BLK MICRO PROCESSOR BOARD DEHUMIDISTAT P2 P5 INTERNAL SEE DEFROST DETAIL WARNING 750 ma MAX FUSE P6 LINE CHASSIS 4 1 T4 T3 T2 T1 TRANSFORMER 1 7 6 12 CONTROLAIR 15 YEL GRN ORN RED BLK DEFROST DETAILS PLUG IN CONNECTOR P1 BLK RED P1 4 3 2 1 PIN 1 BLACK PIN 2 ORANGE PIN 3 RED PIN 4 SPARE PCB...