20/40/60 Minute Timer (99-DET01) Operation:
(1)
Select Button
(2)
20/40/60 minute status lights
Press the Select Button on the timer to initiate high speed ventilation for
20, 40, or 60 minutes. The 20/40/60 minute status lights indicate high
speed operation.
Lockout mode is useful if you wish to disable the timer:
•
Enable Lockout Mode by holding the Select Button for 5 seconds.
•
Disable Lockout Mode by holding the Select Button for 5 seconds.
20/40/60 Minute Timer (99-DET01) Installation:
Connect the wires from the Y, R, and G terminals on the timer to the YEL, RED, and GRN terminals
on the circuit board as shown.
Note
•
Timers mount in standard 2” x 4” electrical boxes.
•
Wire multiple timers individually back to the unit.
•
Use 3 wire; 20-gauge wire (minimum)