ACCESSORIES - FILL CUP EXTENSION KIT(S)

1.

The SGH humidifier is an electrode humidifier.
It produces steam at atmospheric pressure.
Pressure head must develop to push steam
through supply line and into air duct.

2.

Combined resistance of duct positive static
pressure and steam line resistance creates a
small pressure head in steam cylinder. Total
amount of positive static pressure head is
reflected directly by water column differential
that develops between water in the fill cup
hose feeding cylinder and water level in
cylinder.

3.

Standard dimensions of humidifier limit static
that can be tolerated before water will be
pushed high enough to spill over into overflow
tube in fill cup assembly.

4.

To increase allowable water column (allowable
positive static pressure) an accessory Fill Cup
Extension Kit is available from Liebert. See
Figure #22.

CONDENSATE RETURN LINE

1.

Each steam distributor has a built-in
condensate return (3/8" O.D. copper tubing).
Flexible condensate return hose (3/8" I.D.)
available from Liebert, is recommended for
routing condensate back into humidifier’s fill
cup. Note: A short length of 3/8" O.D. copper
tubing is supplied by Liebert for use when
routing condensate hose back to humidifier’s
fill cup. Similarly, a short length of 3/8" I.D.

condensate hose with clamps is supplied with
Liebert’s steam distributors to serve as a
flexible coupling. DO NOT direct solder field
copper condensate line to steam distributors.

2.

Always incorporate a trap in routing of
condensate return line. Condensate that
accumulates in trap will prevent possibility of
steam escaping. Depth of trap must exceed
duct static pressure by 2 inches of water
column. See Figure #23.

3.

Condensate return line can not be run back to
fill cup if humidifier is within 36" of being level
with steam distributor. See Figure #18.

4.

If steam distributor is mounted level with or
below humidifier, condensate line must be
routed to nearest floor drain or to a
condensate pump (available from Liebert).
See Figure #24.

5.

Provide a “U” trap in condensate line even
when distributor is located in return air
plenum. It stops a suction action from

- 8 -

TRAP

3 FEET MINIMUM

CONDENSATE TRAP

DEPTH OF TRAP

MUST BE 2" MORE THAN

DUCT STATIC PRESSURE

OF WATER COLUMN

Figure #23

Trap to Prevent Steam in Condensate Line

HOSEFROMFILLVALVE

FILL CUP BRACKET

FILL CUP

OVERFLOWHOSE

FILL HOSE TO

CYLINDER

Figure #22

Fill Cup Extension Kit to Overcome Static Pressure

Humidifier

Drain Line

Drain

Pump

Floor

Surface

Line

Figure #24

Drain Pump (if necessary)

Содержание SGH Steam

Страница 1: ...Steam Generating Humidifier Installation and Operation Guide IMPORTANT Read and save this guide for future reference This guide to be left with equipment owner SL 14050 Form 99 428 Rev 1 150 1633 Rev...

Страница 2: ...E SUPPLY WIRING TO HUMIDIFIER 9 PRIMARY VOLTAGE SUPPLY WIRING FROM HUMIDIFIER S TO BLOWER PACKS 9 LOW VOLTAGE CONTROL WIRING 9 On Off Controls 9 CONTROL INSTALLATION 10 OPTIONAL MODULATION CONTINUOUS...

Страница 3: ...ight side cover which can also be removed for ease of electrical connection For safety the door when closed keeps the side cover from being removed Single units have a plumbing compartment attached to...

Страница 4: ...ral surface If any spacer material is used between the bracket and the structural material such as drywall increase fastener length accordingly In addition install a minimum of 2 field supplied fasten...

Страница 5: ...stated in the STEAM LINE section on page 6 SGH Model Min Number of Blower Packs Min Overhead Clearance inches cm Min Front Clearance inches cm 010 1 18 45 30 76 020 1 18 45 36 91 050 1 36 91 84 213 1...

Страница 6: ...8 9 The steam distributor mounting plate is perpendicular to the steam distributor When the mounting plate is attached to the side of the duct the distributor is level An upward or downward slope to...

Страница 7: ...y and drain line connections should be installed in accordance with local plumbing codes WATER SUPPLY LINE 1 Humidifier is intended to operate on potable cold tap water 2 If the raw water is very hard...

Страница 8: ...ediment and cause backup The drain line should be 1 O D copper pipe or larger Do not use plastic pipe for drain lines STEAM LINE 1 1 Steam lines for SGH models 010 through 020 require a minimum 7 8 O...

Страница 9: ...nes for SGH 050 through 200 require 1 5 8 O D nominal 1 1 2 copper pipe For steam runs longer than 40 ft use insulated nominal 2 copper to ensure the draining of condensate 8 Do not use steel or plast...

Страница 10: ...t for use when routing condensate hose back to humidifier s fill cup Similarly a short length of 3 8 I D condensate hose with clamps is supplied with Liebert s steam distributors to serve as a flexibl...

Страница 11: ...ier if the blower pack gets overheated The control thermostat mounted on the steam distributor starts the fan when steam is generated 3 All blower packs have high efficiency blowers to minimize the fr...

Страница 12: ...blower pack or air supply grille Do not mount on a outside wall where temperature fluctuation can affect control response 2 Mount duct humidistat in location representative of overall air humidity us...

Страница 13: ...the humidifier starts its operation The controller waits 10 seconds before energizing the on board relays When the relays energize heating voltage is delivered to the cylinder After a 30 second delay...

Страница 14: ...s a set of dry contacts at 61 20 on the control terminal strip The user can connect an indicator externally to 61 20 It will automatically be activated any time a fault is detected DOUBLE UNIT OPERATI...

Страница 15: ...r implied by law No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the...

Страница 16: ...___ Cylinder Last Replaced _________________________ MTH DAY YR _________________________ MTH DAY YR _________________________ MTH DAY YR PRINTED IN CANADA LIEBERT CORPORATION 1050 Dearborn Drive P O...

Отзывы: