Series 600T™ UPS

Multi-Module Three Phase
500 kVA to 750 kVA, 60 Hz

Installation

Manual

Содержание Series 600T

Страница 1: ...POWER PROTECTION Series 600T UPS Multi Module Three Phase 500 kVA to 750 kVA 60 Hz Installation Manual...

Страница 2: ...G MUST BE VERIFIED BY MANU FACTURER PRIOR TO MOVING A BATTERY CABINET Battery cabinets contain non spillable batteries Keep units upright Do not stack Do not tilt Failure to heed this warning could re...

Страница 3: ...15 7 2 Grounding Configuration Delta Source 16 7 3 Preferred Grounding Configuration with Power Tie Switchgear 17 7 4 Grounding Configurations Battery Systems 18 8 0 WIRING CONSIDERATIONS 8 1 Power Wi...

Страница 4: ......

Страница 5: ...Amps 44 Figure 24 Base Mounting Patterns SCCT 3000 Amps 45 Figure 25 Base Mounting Patterns SCCT 4000 Amps 46 Figure 26 Shipping Split Detail 500 kVA Multi Module UPS 12 Pulse Rectifier 47 Figure 27...

Страница 6: ...UPS Video Display Terminal 73 Figure 53 Module Battery Disconnect 600 1200 Amps without Input Isolation Transformer 74 Figure 54 Module Battery Disconnect 300 1200 Amps with Input Isolation Transforme...

Страница 7: ...BINETS ARE INTENDED FOR FORKLIFT USE BASE SLOTS WILL SUPPORT THE UNIT ONLY IF THE FORKS ARE COMPLETELY BENEATH THE UNIT SYSTEM CONTROL CABINETS SCC S HAVE HOLES INTENDED FOR RIGGING BARS OR CHAINS PRE...

Страница 8: ...______________________________________________ kVA Rating ______________________________________________________________ Date Purchased ______________________________________________________________ D...

Страница 9: ...ould be standing on rubber mats The service personnel should wear insu lating shoes for isolation from direct contact with the floor earth ground Unless all power is removed from the equipment one per...

Страница 10: ...batteries should not exceed 25 C 77 F At elevations above 4 000 feet 1219 meters derating may be required consult your Liebert sales representative 5 Even though your Liebert UPS unit is at least 93...

Страница 11: ...Installation Considerations 5 Figure 1 UPS Multi Module Unit Block Diagram...

Страница 12: ...reakers The SCCT is painted the same color as the Liebert UPS but does not match the sheet metal style of the UPS 2 SCCI has the system control logic circuit breakers and static bypass switch integrat...

Страница 13: ...ID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL THE UPS MODULE WEIGHS UP TO 12 000 POUNDS BATTERY CABINETS WEIGH BETWEEN 3100 AND 4900 POUNDS LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING CABINET TEST L...

Страница 14: ...he nameplate on the cabinets to verify that the model numbers correspond with the one specified Record the model numbers and serial numbers in the front of this installation manual A record of this in...

Страница 15: ...ol and dry location 3 Installation and serviceability will be easier if adequate access is provided on all sides of the equipment but only front access is required a Verify that there is adequate clea...

Страница 16: ...can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries 1 Remove watches rings or other metal objects 2 Use tools...

Страница 17: ...e substance toxique les accumulateurs plomb acide devraient tre recycl s plut t qu limin s Il ne faut pas br l le ou les accumulateurs L accumulateur pourrait alors explos Il ne faut pas ouvrir ou end...

Страница 18: ...evront tre observ es 1 Porter toujours des v tements protecteurs ainsi que des lunettes de protection pour les yeux 2 Si l lectrolyte entre en contact avec la peau nettoyer imm diatement en rincant av...

Страница 19: ...ing Electrical codes require that the Battery Cabinet be installed with no less than 3 feet 1 meter of clearance at the front of the cabinet when operating Side and rear panels do not require service...

Страница 20: ...ervice is straight delta or corner grounded delta contact your Liebert representative for details of the Artificial Neutral or Isolated Neutral kits for the System Control Cabinet What are the UPS inp...

Страница 21: ...ion The Maintenance Bypass Switchgear is shown separately for clarity but is usually contained within the System Control Cabinet SCC Notice that the UPS module input and the system bypass input are co...

Страница 22: ...nded delta and there is no intent to operate with one corner of the delta grounded either on purpose or accidentally the SCC requires the Series 600T Artificial Neutral Kit for proper operation This k...

Страница 23: ...kers can be de energized for maintenance Certain con figurations of Power Tie equipment also permit the operator to continuously parallel the output of both UPS systems In tied systems each SCC must h...

Страница 24: ...g on local code requirements Battery cabinet systems on the other hand should be grounded to the UPS module ground bus The figure above illustrates how a simple one cabinet system would be grounded Fo...

Страница 25: ...TO PERSONNEL VERIFY THAT ALL INCOMING HIGH AND LOW VOLTAGE POWER CIRCUITS ARE DE ENERGIZED AND LOCKED OUT BEFORE INSTALLING CABLES OR MAKING ANY ELECTRICAL CONNECTIONS NOTE Use 75 C copper wire Select...

Страница 26: ...Manual c The attachment plug receptacles in the vicinity of the unit or system are all to be of a grounding type and the grounding conductors serving these receptacles are to be connected to earth gro...

Страница 27: ...or the optional SiteScan system Cable group 6 carries signals for the reduced battery charge limit and the reduced input cur rent limit Cable group 7 carries signals to and from the maintenance bypass...

Страница 28: ...CH TIER OF THE LIEBERT BATTERY CABINET IS DISCONNECTED FOR SAFETY DURING SHIPMENT DO NOT COMPLETE THESE CONNECTIONS THE LIEBERT GLOBAL SERVICES REPRESENTATIVE WILL COMPLETE THESE CONNECTIONS AS PART O...

Страница 29: ...KRU RIB BFB MIB Output SBB SBS MBB SCCT can accomodate up to 6 UPS modules To Critical Load Battery MBD SCCT Battery MBD Battery MBD BIB I R 2 UPS CB1 CB2 I R 1 UPS CB1 System Controls I R 3 UPS CB1 C...

Страница 30: ...CB1 RIB RIB BIB RIB SCCI SCCI SCCC can accomodate up to 6 UPS modules Battery MBD Battery MBD Battery MBD MIB To Critical Load SBB SBS MBB System Controls I R 2 UPS CB1 CB2 I R 1 UPS CB1 System Contro...

Страница 31: ...RICIAN EXPERIENCED IN WIRING UPS EQUIPMENT AND IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES IMPROPER WIRING MAY CAUSE DAMAGE TO THE UPS OR INJURY TO PERSONNEL CAUTION All shie...

Страница 32: ...itical load bus Observe phase rotation 12 Control wiring to Remote Monitor Panel if used Selected alarm messages are also available for customer use through a set of contacts on a separate terminal bo...

Страница 33: ...s top entry to bus bars 750 kVA 675 kW and other modules with optional input busbar kit Busbars for AC output Neutral and Ground are provided on the right side of module with top or bottom cable entry...

Страница 34: ...85 310 320 330 355 340 375 385 395 425 385 420 435 450 480 600 700 750 800 900 1000 1250 1500 1750 2000 455 495 520 545 560 545 590 625 650 665 615 665 705 735 750 375 405 435 455 470 445 485 520 545...

Страница 35: ...Installation Drawings 29 11 0 INSTALLATION DRAWINGS Figure 8 Outline Drawing 500 kVA Multi Module UPS 6 Pulse Rectifier...

Страница 36: ...30 Installation Drawings Figure 9 Outline Drawing 500 kVA Multi Module UPS 12 Pulse Rectifier...

Страница 37: ...Installation Drawings 31 Figure 10 Outline Drawing 625 750 kVA Multi Module UPS 6 Pulse Rectifier...

Страница 38: ...32 Installation Drawings Figure 11 Outline Drawing 625 750 kVA Multi Module UPS 12 Pulse Rectifier...

Страница 39: ...Installation Drawings 33 Figure 12 Outline Drawing System Control Cabinet SCCT 200 1200 Amps...

Страница 40: ...34 Installation Drawings Figure 13 Outline Drawing System Control Cabinet SCCT 1600 2500 Amps...

Страница 41: ...Installation Drawings 35 Figure 14 Outline Drawing System Control Cabinet SCCT 3000 Amps...

Страница 42: ...36 Installation Drawings Figure 15 Outline Drawing System Control Cabinet SCCT 4000 Amps...

Страница 43: ...Installation Drawings 37 Figure 16 Battery Power Pack Size A...

Страница 44: ...38 Installation Drawings Figure 17 Battery Power Pack Size B...

Страница 45: ...Installation Drawings 39 Figure 18 Battery Power Pack Three Pack System...

Страница 46: ...40 Installation Drawings Figure 19 Base Mounting Patterns 500 kVA Module 12 Pulse Rectifier...

Страница 47: ...Installation Drawings 41 Figure 20 Base Mounting Patterns 625 750 kVA Module 6 Pulse...

Страница 48: ...42 Installation Drawings Figure 21 Base Mounting Patterns 625 750 kVA Module 12 Pulse Rectifier...

Страница 49: ...Installation Drawings 43 Figure 22 Base Mounting Patterns System Control Cabinets SCCT 200 1200 Amps...

Страница 50: ...44 Installation Drawings Figure 23 Base Mounting Patterns System Control Cabinet SCCT 1600 2500 Amps...

Страница 51: ...Installation Drawings 45 Figure 24 Base Mounting Patterns SCCT 3000 Amps...

Страница 52: ...46 Installation Drawings Figure 25 Base Mounting Patterns SCCT 4000 Amps...

Страница 53: ...Installation Drawings 47 Figure 26 Shipping Split Detail 500 kVA Multi Module UPS 12 Pulse Rectifier...

Страница 54: ...48 Installation Drawings Figure 27 Shipping Split Detail 625 750 kVA Multi Module UPS 6 Pulse Rectifier...

Страница 55: ...Installation Drawings 49 Figure 28 Shipping Split Detail 625 750 kVA Multi Module UPS 12 Pulse Rectifier...

Страница 56: ...50 Installation Drawings Figure 29 Terminal Details 500 kVA Module 6 Pulse Rectifier...

Страница 57: ...Installation Drawings 51 Figure 30 Terminal Details 500 kVA Module 12 Pulse Rectifier...

Страница 58: ...52 Installation Drawings Figure 31 Terminal Details 625 750 kVA Modules 6 Pulse and 12 Pulse...

Страница 59: ...Installation Drawings 53 Figure 32 Terminal Details 750 kVA 675 kW Std and 750 kVA 600 kW with Optional Input Bus Bars...

Страница 60: ...54 Installation Drawings Figure 33 Control Wiring External Interconnections Standard UPS Module...

Страница 61: ...Installation Drawings 55 Figure 34 Control Connection Location 500 kVA Modules...

Страница 62: ...56 Installation Drawings Figure 35 Control Connection Location Diagram 625 750 kVA Modules...

Страница 63: ...Installation Drawings 57 Figure 36 Control Connection Location Diagram SCCC SCCI...

Страница 64: ...58 Installation Drawings Figure 37 Control Connection Location Diagram SCCT...

Страница 65: ...Installation Drawings 59 Figure 38 Control Wire List External Interconnections Standard UPS Module...

Страница 66: ...60 Installation Drawings Figure 39 Control Wire List External Interconnections System Control Cabinet Part 1 of 3...

Страница 67: ...Installation Drawings 61 Figure 40 Control Wire List External Interconnections Standard System Control Cabinet Part 2 of 3...

Страница 68: ...62 Installation Drawings Figure 41 Control Wire List External Interconnections Standard System Control Cabinet Part 3 of 3...

Страница 69: ...Installation Drawings 63 Figure 42 Control Wire List External Interconnections Alarm Status Contacts...

Страница 70: ...64 Installation Drawings Figure 43 Option Wiring Maintenance Bypass Interlock...

Страница 71: ...Installation Drawings 65 Figure 44 Option Wiring Remote Status Panel Interface...

Страница 72: ...66 Installation Drawings Figure 45 Option Wiring Internal Modem...

Страница 73: ...Installation Drawings 67 Figure 46 Option Wiring Customer Alarm Interface SCC with Momentary Duty Static Switch...

Страница 74: ...68 Installation Drawings Figure 47 Option Wiring Customer Alarm Interface SCC with Continuous Duty Static Switch...

Страница 75: ...Installation Drawings 69 Figure 48 Option Wiring Battery Temperature Sensor...

Страница 76: ...70 Installation Drawings Figure 49 Option Wiring SNMP Interface...

Страница 77: ...Installation Drawings 71 Figure 50 External Interconnections Module 1 SCC Cable Groups 21 and 22...

Страница 78: ...72 Installation Drawings Figure 51 External Interconnections Module 2 SCC Cable Groups 21 and 22...

Страница 79: ...Installation Drawings 73 Figure 52 Wiring Configurations UPS Video Display Terminal...

Страница 80: ...74 Installation Drawings Figure 53 Module Battery Disconnect 600 1200 Amps without Input Isolation Transformer...

Страница 81: ...Installation Drawings 75 Figure 54 Module Battery Disconnect 300 1200 Amps with Input Isolation Transformer...

Страница 82: ...76 Installation Drawings Figure 55 Remote Status Panel Surface Mount...

Страница 83: ...Installation Drawings 77 Figure 56 Circuit Breaker Schedule Multi Module UPS 300 750 kVA...

Страница 84: ...78 Installation Drawings Figure 57 Circuit Breaker Schedule Merlin Gerin Breakers SCCT 200 4000 Amps...

Страница 85: ...Installation Drawings 79 Figure 58 Circuit Breaker Schedule General Electric Breakers SCCT 200 4000 Amps...

Страница 86: ...2 0 volt line drop measured at the module at maximum discharge current 7 Grounding conductors to be sized per NEC 250 122 Neutral conductors to be sized for full capacity for systems with 4 wire loads...

Страница 87: ...1 214 103 250 72x39x79 5 930 304 500 450 480 NO YES 688 861 601 752 1 200 1 214 124 550 96x39x79 9 030 347 500 450 480 YES YES 638 798 601 752 1 200 1 214 129 931 96x39x79 9 230 355 625 500 480 NO NO...

Страница 88: ...200 1 214 112 050 72x39x79 6 330 325 500 450 600 NO YES 551 688 481 601 1 200 1 214 124 550 96x39x79 9 030 347 500 450 600 YES YES 510 638 481 601 1 200 1 214 129 950 96x39x79 9 230 355 625 500 600 N...

Страница 89: ...8 1 10 L973 12 714255 76 4 4 0 AWG 3 8 1 20 M973 12 714255 86 5 Color Keyed Aluminum Copper 1 0 AWG 3 8 0 93 60130 6 2 0 AWG 3 8 0 97 60136 7 3 0 AWG 3 8 1 06 60142 8 Color Keyed Copper Cable Long Ba...

Страница 90: ...84 Appendix B Field Supplied Lugs...

Страница 91: ...pport through more than 100 service centers around the world and a 24 hour Customer Response Center While every precaution has been taken to ensure accuracy and completeness of this literature Liebert...

Отзывы: