![Liebert NX 10kVA Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/liebert/nx-10kva/nx-10kva_installation-manual_1907521046.webp)
Options
40
Figure 22 Battery circuit breaker box connections
NOTE
1. The signal cables in this figure must be shielded and double-insulated.
2. Connect the Pes (Protection Earth) of the UPS cabinet and BCB box to the same point.
ISOMETRIC VIEW W/O TO & COVER
(-
)
CIRCUIT
BREAKER
(+
)
(-)
(GN
D)
(+)
(-)
8.34"
211.72mm
.38"
9.53mm
3.98"
101.2mm
3.86"
97.95mm
5.39"
137mm
5.39"
137mm
.38"
9.53mm
31.50"
800.1mm
(MTG DIM.)
32.25"
819.15mm
2.62"
66.62mm
15.00"
381mm
(MTG DIM.)
20.24"
514.21mm
O
.31"
7.92mm (TYP. .25" HDWR)
REMOVEABLE
COVER
CONDUIT ENTRY
TOP & BOTTOM
3
TB1
CUSTOMER GROUND
.25" STUD FOR
6GA - 2/0 WIRE
O
.50"
12.7mm
X6
(+
)
(-
)
(+
)
FROM CUSTOMER'S
BATTERY SYSTEM
(FIELD INSTALLED)
(FIELD SUPPLIED)
CONNECT TO UPS MODULE
(FIELD INSTALLED)
1
2
3
4
5
6
TB1
N.C. BLUE
N.O. RED
COM BLACK
30
2
303
(-)
(-)
(+)
(+)
NE
UTA
L
1. HARDWARE FOR CONNECTING CABLES TO THE BREAKER SUPPLIED.
2. "TYPE-1" RATED ENCLOSURE.
3. LOW VOLTAGE WIRING NEEDS TO ENTER THIS BOX FROM THE TOP.
4. DC OUTPUT POWER CONNECTIONS WILL ACCEPT (2) POSITIVE AND (2) NEGATIVE
WIRES, ACCEPT 2GA.
5. DC INPUT CONNECTION WILL ACCEPT 2GA WIRE FOR 10 -15KVA UPS WITH 70A BREAKER,
OR 20-30KVA UPS WITH 125A BREAKER.
NEUTRAL BUSBAR
NEUTRAL
BUSBAR
Содержание NX 10kVA
Страница 1: ...POWER AVAILABILITY NX INSTALLATION MANUAL 10 30kVA 208V 60Hz...
Страница 54: ...Installation Drawings 48 Figure 27 Location of internal batteries Battery 417mm 687mm 186...
Страница 64: ...Specifications and Technical Data 58 NOTES...
Страница 65: ...Specifications and Technical Data 59...
Страница 66: ...Specifications and Technical Data 60...
Страница 67: ......