Liebert LM250120YARCE Скачать руководство пользователя страница 1

 

Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH  43229  
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169 
EMAIL: [email protected] • Web Site: www.Liebert.com    

82241 Rev 1

 

 

Example Part Number:    

LM250120YARCE

 

500kA per Phase (250kA per Mode), 
120/208V 3-Phase Wye, All Mode, 
Rotary Disconnect, LED’s, Alarm, 

 

Counter, & Dual Form C Contacts,  
NEMA 12 Enclosure

 

Liebert LM Series TVSS

 

Technical Specification

  

Maximum Continuous  
Operating Voltage (MCOV) 
...................... 120V 125%, all others 115% 
Fault Current Rating (AIC)....................... 200 kAIC 
Operating Frequency Range ................... 47 – 63 Hz 
Response Time ........................................ <0.5 ns 
Operating Humidity.................................. 0% to 95% 
Status Indication ...................................... LEDs, Audible Alarm, Dry Contacts  
Certifications ............................................ UL 1449 & 1283, CUL, NEMA LS1, 
                                                                     ISO 9001:2000 
Enclosure  ................................................ NEMA 12 
Warranty ................................................... 5 Years Parts 

 

 

UL 1449 second edition clamping data 

Configuration 

L-N 

L-G 

L-L 

N-G 

120S, 120Y 

400 

400 

700 

400 

240D 

700 

700 

346Y 

1200 

1200 

2000 

1200

 

230Y, 277Y 

700 

700 

1500 

700 

480D 

1500 

1500 

600D 

1800 

2000 

 

Job Name ____________________________

Model# ______________________________

Date ________________________________

Qty _________________________________

Quote# ______________________________

Source Configuration 

1 Phase, L-N, 2W+G 

N

 

1 Phase, L-L, 2W+G 

L

 

Split Phase, 3W+G 

S

 

3 Phase, WYE, 4W+G 

Y

 

3 Phase, WYE, 3W+G   

(No Neutral) 

X

 

3 Phase, Delta, 3W+G 

D

 

3 Phase, Delta Hi-leg, 4W+G 

H

 

 

Surge Rating 

60kA / 
mode 

060 

80kA / 
mode 

080 

100kA / 
mode 

100 

125kA / 
mode 

125 

150kA / 
mode 

150 

200kA / 
mode 

200 

225kA / 
mode 

225 

250kA / 
mode 

250 

 

Model # LM

    __ __ __    __ __ __   __   __   __   __   __ 

Modes of Protection 

All 

 

L-G Voltage

 

120V

 

120

 

208V  

208 

220V  

230 

230V  

230 

240V  

240 

277V  

277 

480V  

480 

600V 

600 

 

Connection Options 

Wire Lug 

Disconnect 

 

Enclosure 

NEMA 12 

(Standard) 

NEMA 3R 

NEMA 4 

NEMA 4X 

 

Monitoring Options 

Standard Monitoring System, 
LEDs, Audible Alarm,  
Dual Form C Contacts 

LEDs, Audible Alarm,  
Surge Counter,  
Dual Form C Contacts 

 

Dimensional data in inches and shipping weight in pounds 

Unit 

Options 

Wt. 

LM060 
LM080 

All 

16 

14 

16.75 

12 

0.31 

1.35 

32 

LM100 
LM125 
LM150 

All 

16 

14 

16.75 

12 

0.31 

1.84 

41 

LM200 
LM225 
LM250 

All 

20 

16 

21.25 

10 

0.44 

1.84 

56 

Life Cycle Surge Testing 

10kA, 20kV, IEEE Cat. C3 

Unit 

Per Mode 

Per Phase 

060-080 

8,000 

16,000 

100-150 

16,000 

32,000 

200-250 

24,000 

48,000 

EMI/RFI Noise Rejection 

Single 

Unit 

Frequency 

System 

Installation 

34dB 

100kHz 

51dB 

51dB 

1MHz 

94dB 

54dB 

10MHz 

114dB 

48dB

 

100MHz

 

120dB

 

E

 

D

 

C

 

B

 

G

A

 

F

 

Отзывы: