Страница 2: ...ontact the nearest Emerson local sales office or service center Copyright 2010 by Emerson Network Power Co Ltd All rights reserved The contents in this document are subject to change without notice Em...

Страница 3: ......

Страница 4: ...ntenance and servicing procedures of the equipment should be carried out only by trained personnel with tools Components including the components behind the protective cover which can only be removed...

Страница 5: ...UPS Commissioning 12 2 4 1 Check Before Startup 12 2 4 2 Single UPS Parameters Setting 12 2 4 3 Normal Mode Startup 16 2 4 4 Battery Mode Startup 17 Chapter 3 Parallel UPS Installation And Commissioni...

Страница 6: ...y panel Ventilation hole Figure 1 1 Front panel of the UPS The rear panel of the UPS is shown in Figure 1 2 Input switch 230 400Vac 40A Battery port 192Vdc 27A PE Parallel port with protective cover V...

Страница 7: ...Remove the screws of the UPS top plate or open the chassis z Slotted screwdriver EJ375mm Connect input and output cables z Diagonal plier MTC3C Make input and output cables z Wire pressure plier YT 12...

Страница 8: ...panel of the UPS according to the arrow direction as shown in Figure 2 2 Square hole Plastic panel Display panel Figure 2 2 Installing the plastic panel Note You do not need to remove UPS when removi...

Страница 9: ...ke out the brackets and eight M4 10 screws from the accessories Through the installation hole 1 use M4 10 screws to fix the two brackets respectively on both sides of the UPS front panel as shown in F...

Страница 10: ...through the guide rail screws a total of eight each left and right guide rail needs four guide rail screws as shown in Figure 2 9 Guide rail screw 4 pcs Guide rail Guide rail holder Square hole Figure...

Страница 11: ...necting Power Cables I O cables battery cables and external 10A charger cable optional are required for connection When connecting the cables you should follow the local wiring regulations take the en...

Страница 12: ...accessory of the UPS is required for all cable connections 2 3 1 Connecting I O Cables Notes 1 Do not reverse the input neutral line and live line 2 Do not use a wall socket to feed power to the UPS...

Страница 13: ...ine terminal U input ground line terminal of the UPS I O terminal block and tighten the fixing screws Short the input live line terminal V input live line terminal W and input live line terminal U1 us...

Страница 14: ...17 Warning he DC battery MCB must be added between the battery string and UPS First cell Second cell Third cell Sixteenth cell UPS Bat Battery module Bat Figure 2 17 Battery module connection principl...

Страница 15: ...ng time delaying UPS battery cabinet is used Long time delaying UPS provides a battery cable B which has a PP45 plug on one end and three OT terminals on the other end as shown in Figure 2 20 It is us...

Страница 16: ...rear panel of the UPS and insert the other end of the cable into the control port of 10A charger as shown in Figure 2 22 Paralleled address Control port Input switch 230 400Vac 40A Intellislot Battery...

Страница 17: ...meters Setting Parameters setting of the standard LED display panel There are LED indicators and functional keys on the LED display panel as shown in Figure 2 24 ON SILENCE key OFF key 8 Battery indic...

Страница 18: ...ult f Parallel current sharing failure f Rectifier failure bus voltage abnormal f Battery fault high voltage f Battery fault no battery reverse connection f Other failures auxiliary power supply failu...

Страница 19: ...tery self test OFFkey 1 Turning off inverter When the UPS is in normal mode or battery mode pressing and holding this key for one second turns off the inverter then the UPS turns to the bypass mode 2...

Страница 20: ...shed every other second Input Input voltage Phase A Phase B Phase C Input frequency Output Output voltage Output current Output frequency Active power Apparent output Load factor Battery Battery volta...

Страница 21: ...equencys of the UPS are available 50Hz and 60Hz Select the appropriate output frequency according to the input frequency there is no need to set 2 When power on at the first time you should adopt norm...

Страница 22: ...the UPS will start up and enter the self test status including battery self test All LED indicators blink the buzzer beeps at intervals After the self test the UPS will enter the standby mode 2 Press...

Страница 23: ...llation method of 3 1 parallel UPS is the same as that of the single UPS Refer to 2 2 Mechanical Installation for details 2 As shown in Figure 3 1 the battery module should be installed at the bottom...

Страница 24: ...ion unit Figure 3 2 Block diagram of four UPS parallel system 3 2 2 Connecting Parallel Cables The parallel system provides parallel cables The parallel cables form a ring connection through the paral...

Страница 25: ...circuit 2 Check that the battery installation and cable connection are correct and there is no short circuit and that battery polarity is correct 3 Check that the phase sequence of the mains bypass a...

Страница 26: ...rallel POD is configured close the corresponding input MCB and output MCB of the POD the UPS is powered on at the same time make sure that other UPSs are in the shutdown status After the self test pre...

Страница 27: ...e USB communication cable into the USB port of the computer Before communication you need to install USB drive program delivered in the installation disk The USB port can connect the standalone licens...

Страница 28: ...les improperly connected Check that the external battery cables are properly connected External battery polarity reversed Check that the external battery cables are not reverse connected 7 The fault i...

Страница 29: ...buzzer beeps for a long time The parallel address is wrong 1 Open the UPS mains switch 2 Reset the parallel address Overload Remove some loads restart UPS after five minutes 16 The fault indicator ill...

Страница 30: ......