6 | EN

Copyright © Liberty Pumps, Inc. 2020 All rights reserved.

6850000C

 Seal Failure Probes

XLSG/XLSGX-Series grinder pumps are equipped with two 

mechanical face seals with an intermediate oil chamber between 

them. This ensures lubrication for the seals, shaft flame path, and 

as a barrier to the motor chamber in the event the lower seal is 

compromised. A seal fail or moisture sensing device is located in 

the mid oil chamber and continuously monitors for leakage. In the 

event of a seal failure, moisture mixes with the oil, tripping the 

seal leak circuit. In a failure condition, a fault light will illuminate 

on the control panel. The pump will continue to operate, but 

service should be scheduled as soon as possible.
Intrinsically safe (ISS and ISD) control panels by Liberty Pumps 

have a seal leak test button that tests the integrity of the seal leak 

circuit continuity. When pressed, the light should illuminate. The 

light should go off when the test button is released. If it remains 

on, the potentiometer is set too high. If light does not illuminate, 

the light is burned out, the circuitry is open, or the system does 

not have power. The seal leak relay requires adjustment upon 

installation. See 

Seal leak relay setup 

on page 7.

 Power and Control Cords

 

Do not remove cord and strain relief, and do not connect 

conduit to pump.

 

The power and control cords cannot be spliced; a junction box 

may be used providing it is rated for hazardous locations and has 

approved cord connectors.

IMPORTANT: 

Each cord has a green lead. This is the ground wire 

and must be grounded properly per NEC

®

 and/or local codes.

Wiring Instructions

 

 

Always disconnect pump(s) from power source(s) before 

handling or making any adjustments to either the pump(s), 

the pump system, or the control panel.

 

All installation and maintenance of pumps, controls, 

protection devices, and general wiring shall be done by 

qualified personnel.

 

All electrical and safety practices shall be in accordance with 

the National Electrical Code

®

, the Occupational Safety and 

Health Administration, or applicable local codes and 

ordinances.

 

 Figure 1. Wiring Diagram 1-Phase

 Figure 2. Wiring Diagram 3-Phase

RISK OF ELECTRIC SHOCK

RISK OF ELECTRIC SHOCK

WHITE

WHITE

GREEN

BLACK

GREEN

GREEN

BLACK

GREEN

NOT 

USED

*

NOT 

USED

*

* Note: 

On 

1-phase 
pumps, the 
white and red 
leads of the 
control cord 
are not used.

SEAL 

LEAK

BLACK

WHITE

RED

MOTOR

BLACK

WHITE

RED

RED

WHITE

GREEN

BLACK

L2/N

L1

RUN 
CAP

START 
CAP

POTTING 

RESIN

SEAL 

FAILURE 

PROBES

START 

RELAY

5          2

1

CONTROL 

CORD 

POWER 

CORD

START CIRCUIT

START CIRCUIT

SEAL FAILURE

PROBES

MOTOR

SEAL LEAK

POWER

CORD

CONTROL

CORD

WHITE

WHITE

WHITE

WHITE

GREEN

GREEN

RED

RED

RED

RED

WHITE

WHITE

GREEN

GREEN

BL

A

C

K

BL

A

C

K

BL

A

C

K

BL

A

C

K

POTTING

RESIN

L3

L2

L1

THERMOSTAT

THERMOSTAT

L3

L2

L1

BLK

PNK

VIO

RED

WHT

BLU

BRN

ORN

YEL

440–480V 3PH

L3

L2

L1

BLK

PNK

VIO

575V 3PH

BLK

PNK

VIO

RED

WHT

BLU

BRN

ORN

YEL

L3

L2

L1

208V/230V 3PH

Содержание Omnivore XLSG Series

Страница 1: ...placement manual visit LibertyPumps com or contact Liberty Pumps at 800 543 2550 Retain dated sales receipt for warranty Model 7000 Apple Tree Avenue Bergen NY 14416 ph 800 543 2550 fax 585 494 1839 w...

Страница 2: ...by its power cord This will damage the power cord and could expose the electrically live wires inside the power cord The electrical power supply shall be located within the length limitations of the p...

Страница 3: ...motor enclosures Refer to Chapter 5 of the National Electric Code or applicable local codes and ordinances for all electrical and wiring requirements in hazardous locations Float switches must be conn...

Страница 4: ...sings causing surroundings to become energized At no time shall the pump be stored within an incomplete wet pit The pump should not be placed into the pit until it can be fully operational Do not allo...

Страница 5: ...void the T4 temperature class of the pump and will drop the temperature class to T3 200 C Intrinsically safe control panels designed for use with the XLSG XLSGX Series pumps available from Liberty Pum...

Страница 6: ...cords cannot be spliced a junction box may be used providing it is rated for hazardous locations and has approved cord connectors IMPORTANT Each cord has a green lead This is the ground wire and must...

Страница 7: ...he cutter Besides verification that the cutter and impeller are freely spinning rotating the cutter helps to lubricate the shaft seals if the pump has been non operational for more than a week It is r...

Страница 8: ...ected serious damage injury or death can result when power is applied Starting System 1 Verify all plumbing components in the basin are installed correctly and functional Verify all valves are open an...

Страница 9: ...ds warranty Table 2 Troubleshooting Matrix Problem Possible Cause Corrective Action Pump does not start Damaged power cable Return pump to an authorized repair facility Control panel selector switch i...

Страница 10: ...scharge line is blocked or restricted Check the discharge line for foreign material including ice if the discharge line passes through or into cold areas Check valve is stuck closed or installed backw...

Страница 11: ...cation Pump is being run below minimum head requirement causing cavitation A different sized pump or impeller may be required Consult Liberty Pumps Foreign objects in the impeller cavity Clean the imp...

Страница 12: ...operated or maintained per manufacturer instructions if it has been disassembled modified abused or tampered with if the electrical cord has been cut damaged or spliced if the pump discharge has been...

Отзывы: