background image

7550000G

Copyright © Liberty Pumps, Inc. 2022 All rights reserved.

9 | EN

 3-Phase Pump Rotation Verification

Verify 3-phase pumps for correct rotation prior to installing 

pump(s) in basin. To change rotation, reverse any two of the 

three power leads to the pump (not the ground). Code the 

wires for reconnection after installation.

3-phase power uses three separate alternating currents that peak 

at different integrals. With pumps that are powered by 3-phase 

electric, the phase sequence of the motor must match the phase 

sequence of the power source. When the phase sequences match, 

the pump operates properly. However, when the phases are out of 

order, the pump runs backward (i.e., the impeller rotates in the 

wrong direction). This causes an extreme loss of performance and 

could raise the current draw, which could result in tripping an 

overload or circuit breaker.
To ensure that the power to the pump is installed correctly, always 

verify proper rotation 

before

 lowering it into the basin. If the 

pump is rotating in the wrong direction, turn off the power and 

reverse any two of the three power leads to the pump (not the 

ground). This reverses the phase sequence and corrects the pump 

rotation. 

For 3-phase pumps, rotation must be clockwise when 

looking from the top of the pump. The correct direction is also 

stamped on the bottom of the volute.

 Discharge

Make all discharge connections. A check valve is required to 

prevent the backflow of liquid after each pumping cycle. A gate 

valve should follow the check valve to allow periodic cleaning of 

the check valve or removal of the pump. The remainder of the 

discharge line should be as short as possible with a minimum 

number of turns to minimize friction head loss. Do not reduce the 

discharge to below the pump outlet size. Larger pipe sizes may be 

required to eliminate friction head loss over long runs. Contact 

Liberty Pumps or other qualified person if questions arise 

regarding proper pipe size and flow rates.

 Pressure Sewer Applications 

A redundant check valve assembly consisting of a curb stop and 

check valve must be installed between the pump discharge and 

the street main, as close to the public right-of-way as possible, on 

all pressure (force main) sewer installations to protect from system 

pressures. The curb stop valve is necessary to isolate the site from 

the pressure sewer while the check valve provides redundant 

protection against potentially detrimental backflow. All valves and 

fittings should be rated for at least 200 PSI service. See Liberty 

Pumps line of CSV-Series Curb Stop/Swing Check Valve 

Assemblies and CK-Series Connection Kit.

 Vent

The fiberglass basin provided with the system must be completely 

sealed and properly vented per local health and plumbing code 

requirements. If the system is to be vented through the inlet to an 

existing building vent stack, there must be no traps between the 

system inlet and the nearest building vent stack connection 

(option 1). If this is not possible or desirable per the application, a 

standalone vent can be installed in tank side (option 2) or a vent 

flange or grommet can be installed in a hole cut into the cover 

(option 3).

Correct Impeller Rotation

BOTTOM VIEW

TOP VIEW

Bulkhead 
Connection

Pump Station

Compression 

Adapter 

Fitting

Curb Box

Compression 

Adapter 

Fitting

Valve Extension 
Rod Shown

Curb Stop Valve/Swing 

Check Valve Assembly

To Pump

To Main

Flow

Grade

 

option 1

option 2

option 3

Discharge

ground level

Sewage line

Содержание LGH Series

Страница 1: ... system pressures Installer manual must remain with owner or system operator maintainer Record information from pump nameplate Model Serial Control Panel Mfg Date Install Date Dealer Dealer Ph 7000 Apple Tree Avenue Bergen NY 14416 ph 1 800 543 2550 fax 1 585 494 1839 www LibertyPumps com LEP 60 Hz 7550000G LGV Series LGH Series Ordinary Location Models XLGV Series XLGH Series Approved for Hazardo...

Страница 2: ...wer cord and could expose the electrically live wires inside the power cord The electrical power supply shall be located within the length limitations of the pump power cord and for below grade installations it shall be at least 4 ft 1 22 m above floor level Do not use this product in applications where human contact with the pumped fluid is common such as swimming pools fountains marine areas etc...

Страница 3: ... careful around pump base while power is connected Make sure that the pump is either in the tank or clear from people and wires when in operation Wear adequate Personal Protective Equipment when working on pumps or piping that have been exposed to wastewater Sump and sewage pumps often handle materials that can transmit illness or disease upon contact with skin and other tissues Do not enter a pum...

Страница 4: ...t trim impellers without consulting the factory Model Specifications For complete listing of models and their specifications refer to www LibertyPumps com lep About Engineering Specs Pump nameplate provides a record of specific pump information Inspection and Storage Initial Inspection The pump should be immediately inspected for damage that may have occurred in shipment 1 Visually check the pump ...

Страница 5: ...onents can be purchased separately using the part numbers shown Other options such as pre wired kits are also available Control Panels in Hazardous Locations Float switches must be connected to an intrinsically safe circuit in the control panel as per the requirements of Chapter 5 of the National Electric Code For hazardous locations the control panel must be installed outside the hazardous area a...

Страница 6: ... the pump will continue to operate but service should be scheduled as soon as possible The LEP Series control panels by Liberty Pumps have a seal leak detection system with a test button that monitors the integrity of the seal leak circuit and components When pressed the light should illuminate The light should go off when the test button is released If it remains on the potentiometer is set too h...

Страница 7: ...K POTTING RESIN RED WHITE ORANGE RUN CAP 80 MFD 370 VAC START CAP 270 324 MFD 330 VAC SEAL LEAK POWER CORD CONTROL CABLE ORANGE RED RED WHITE WHITE GREEN GREEN BLACK BLACK THERMOSTAT M3 M2 M1 L3 L2 L1 MOTOR GRAY BROWN BROWN GREEN GRAY THERMOSTAT SEAL FAILURE PROBES POTTING RESIN FOR HAZLOC PUMPS M3 M2 M1 1 6 7 2 4 8 3 5 9 200 230V 3PH 2D 460V 3PH 1D 15HP MODELS ONLY M3 M2 M1 1 1 2 2 3 1 2 3 3 7 7 ...

Страница 8: ...e 1 and Figure 2 Figure 1 Cut off Point 3 7 hp Pumps Figure 2 Cut off Point 10 15 hp Pumps Cutter and Impeller Free Movement Check Wear Personal Protective Equipment to protect hands as cutter blades have extremely sharp edges and present a serious cutting hazard Do not connect any power to pump until this check is complete Manually rotate the cutter and impeller to check that they spin freely wit...

Страница 9: ... as short as possible with a minimum number of turns to minimize friction head loss Do not reduce the discharge to below the pump outlet size Larger pipe sizes may be required to eliminate friction head loss over long runs Contact Liberty Pumps or other qualified person if questions arise regarding proper pipe size and flow rates Pressure Sewer Applications A redundant check valve assembly consist...

Страница 10: ...le of operation 7 Turn H O A switch es to OFF position and allow basin to fill to the override alarm control level s 8 Observe all floats in operation to verify that there is adequate clearance to the surrounds to ensure that the floats do not have the opportunity to get hung up in their travel 9 Verify alarm system response 10 Turn switch es to AUTO position pumps should start and operate togethe...

Страница 11: ...ps The only allowable repairs replacements without compromising the hazardous location rating of the pump are Quick connect cords lower outer shaft seals volute and impeller components Otherwise the pump must be returned to Liberty Pumps or an authorized hazardous repair facility for electrical and motor service This will ensure the integrity of the hazardous location rating of the pump and comply...

Страница 12: ...ctive float switch Replace float switch Missing or faulty curb stop swing check valve allowing system pressure to feed back through discharge piping Verify presence of a curb stop check valve or replace curb stop swing check valve assembly Pump operates with selector switch in Hand position but does not operate in Auto position Control circuits malfunctioning Check float switch level control or al...

Страница 13: ...essure to feed back through discharge piping Verify presence of a curb stop check valve or replace curb stop swing check valve assembly Pump runs periodically when fixtures are not in use Check valve not installed stuck open or leaking Install check valve s remove check valve and examine for freedom of operation and proper installation Fixtures are leaking Repair fixtures as required to eliminate ...

Страница 14: ... gravel or other abrasives if the product has been used to pump chemicals or hydrocarbons if the product has been moved from its original installation location or if the label bearing the serial and code number has been removed Liberty Pumps Inc shall not be liable for any loss damage or expenses resulting from installation or use of its products or for consequential damages including field labor ...

Отзывы: