Installation 

Manual

For pressure sewer applications

, verify a Redundant 

Check Valve Assembly (curb stop and check valve) is 

installed between the pump discharge and the street 

main, as close to the public right-of-way as possible, on all 

installations to protect from system pressures.

Installer: manual must remain with owner or 

system operator/maintainer.

Record information from pump nameplate:

Model:

Serial: 

Control Panel:

Mfg Date:

Install Date:

Dealer:

Dealer Ph:

7000 Apple Tree Avenue
Bergen, NY 14416
ph: 1-800-543-2550
fax: 1-585-494-1839
www.LibertyPumps.com/LEP

60 Hz

1620000B

Liberty 

Engineered 

Pump 

Systems 

(LEPS)

for Ordinary and 

Hazardous Locations

Common Components

Fiberglass Basin 

Sewage or Grinder Pump(s)

Inlet Hub

Control Panel

Alarm System

NEMA 4X Junction Box

Pre-Mounted Float System

Factory Installed Guide Rail System

Содержание LEPS Series

Страница 1: ...aller manual must remain with owner or system operator maintainer Record information from pump nameplate Model Serial Control Panel Mfg Date Install Date Dealer Dealer Ph 7000 Apple Tree Avenue Bergen NY 14416 ph 1 800 543 2550 fax 1 585 494 1839 www LibertyPumps com LEP 60 Hz 1620000B Liberty Engineered Pump Systems LEPS for Ordinary and Hazardous Locations Common Components Fiberglass Basin Sewa...

Страница 2: ...s controls protection devices and general wiring shall be done by qualified personnel All electrical and safety practices shall be in accordance with the National Electrical Code the Occupational Safety and Health Administration or applicable local codes and ordinances Do not remove cord and strain relief and do not connect conduit to pump Pump shall be properly grounded using its supplied groundi...

Страница 3: ...es that are poisonous This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm www p65warnings ca gov Do not remove any tags or labels from the pump or its cord A grinder pump contains metal parts that rotate at high speeds Be careful around pump base while power is connected Make sure that the pump is either in the tank or clear...

Страница 4: ...nd date Pump tags are located on the pump s Duplicate pump tags are packaged with the system These should be mounted on the basin cover or the control panel for accessibility and immediate pump information Inspection Inspect the system upon arrival to ensure that there is no shipping damage Pay careful attention to the condition of the fiberglass basin control floats pump guide rail brackets and c...

Страница 5: ...tten authorization Excavated Materials Handling Carefully store excavated materials that cannot be removed from the job site as far from the edge of the basin excavation as possible Unless approved for use as backfill securely store excavation materials separate from the approved backfill materials Work Area Safety Safe installation procedures are the sole responsibility of the basin installer Wor...

Страница 6: ...excavation and safety considerations Basin anti flotation flange Compacted sub base and or concrete slab as per engineer s specification FINISH GRADE 12 minimum backfill compacted to a minimum soil modulus of 700 lbs per sq ft Fiberglass basin as required per engineer s specification Backfill material Concrete grout as required per engineer s specification CAUTION HANDLE WITH CARE Do NOT drop Do N...

Страница 7: ...loat control panel in a simplex 4 float control panel in a duplex or 6 float control panel in a quadplex configuration Correct height settings for each float are critical for optimal pump cycling and operation of the system Since basin heights vary with each system use the centerline of the inlet hub as the baseline for measuring the distance of the top two floats ALARM and ON The lowest float OFF...

Страница 8: ...For 3 phase pumps rotation must be counter clockwise when looking from the bottom clockwise when looking from top of the pump Discharge Connect Schedule 80 PVC pipe to the pump discharge Do not increase the discharge piping to a larger size than the pump can handle Do not reduce the discharge to below the pump outlet size The remainder of the discharge line should be as short as possible with a mi...

Страница 9: ...to the cover option 3 System option 1 option 2 option 3 Discharge ground level Sewage line LEPS GR Series Guide Rail System The optional GR20 GR3 or GR4 quick disconnect assembly guide rail system supplied with the LEPS is designed to allow easy installation and removal of the pump When installed correctly it seals and provides a means to lift the pump without disconnecting any of the discharge pi...

Страница 10: ...PS GR Series Guide Rail System Check voltage at panel When pumps need to be installed long distances from a power source attention must be given to properly size the wire Considerations must be made for the pump s required voltage phase full load amps and length of wire Proper sizing should be done by an electrician although using a sizing tool as a guide provides a close approximation This would ...

Страница 11: ... will automatically run the pump no matter what the current liquid level is while the OFF mode does the opposite The AUTO mode is the normal operation mode In AUTO mode the floats or in some cases transducer will trigger the control panel to operate the pump turning ON when the liquid level reaches a certain height and turning OFF when the liquid level falls to a certain height If the pump is not ...

Страница 12: ...om the factory or an authorized Liberty Pumps repair facility There is no other express warranty All implied warranties including those of merchantability and fitness for a particular purpose are limited to 18 months from the date of installation or 24 months from the manufacturing date This Warranty contains the exclusive remedy of the purchaser and where permitted liability for consequential or ...