6
SETTING AND USING METHOD
ENGLISH
NOTE
!
Default status is all off.
• L4 : Set Operating status output.
②
Setting of SW102 :
Using SW102 set the internal function as
described below.
• L1 : Set Analog output default value when
Communication Error will be occur
(Module – ODU)
①
Setting of SW101:
Using SW101 select the option of control
function as described below.
• L3 : Set low Noise operation.
This is a function driving outdoor unit
fan RPM to operate low speed for
reducing fan noise according to the
input signal. To use this function, you
should set outdoor unit mode, please
refer to PDB more detail.
SETTING AND USING
METHOD
L1
ON
2
3
4
L1
ON
2
Position
Function
ON
L1 2
3 4
ON : Enable Low Noise
Operation
OFF : Disable Low Noise
Operation
Position
Function
ON
L1 2
3 4
ON : Activate Digital Output
according to Indoor Unit status
OFF : Activate Digital Output
according to Outdoor Unit sta-
tus
CAUTION
After change Dip SW setting, press reset
switch to reflect the setting.
!
CAUTION
If the Dip SW is set , IO module System
is operating preferentially than outdoor
unit setting.
!
Position
Function
ON
L1 2
ON : Analog output 0V
OFF : Analog output 10V
Position
Function
ON
L1 2
ON : Ignore minimum Analog output
value setting (L1,L2 setting
value of 4pin Dip SW)
OFF : Follow minimum Analog out-
put value setting (L1,L2 set-
ting value of 4pin Dip SW)
• L2 : Set Analog output Range
Basically this module keeps a minimum
Analog output voltage refer to L1,L2 setting
of SW101 to prevent unexpected accident.
When you need to use 0~10V full range, L2
should be set as ON.
CAUTION
After change Dip SW setting, press reset
switch to reflect the setting.
!
(1) MFL67888703 (영영) 2017. 5. 31. 영영 6:51 Page 6