14
SETTING AND USING METHOD
ENGLISH
- Detail of the control step for analog input signal
SW_ STEP
Input Voltage
Cooling
Heating
Type of input
Evaporating
Temp. [°C]
Operation rate
Condensing
Temp. [°C]
Operation rate
C
0
Comp off
0%
Comp off
0%
Analog input
1
Comp off
Comp off
2
Comp off
Comp off
3
11.0
40%
31.3
40%
4
9.8
45%
33.3
45%
5
9.0
50%
34.5
50%
6
7.2
60%
37.5
60%
7
5.9
70%
40.4
70%
8
5.0
80%
43.1
80%
9
4.1
90%
45.6
90%
10
3.1
100%
48.1
100%
D
0
No control
-
No control
-
Analog input
1
3.1
100%
48.1
100%
2
4.1
90%
45.6
90%
3
5.0
80%
43.1
80%
4
5.9
70%
40.4
70%
5
7.2
60%
37.5
60%
6
9.0
50%
34.5
50%
7
9.8
45%
33.3
45%
8
11.0
40%
31.3
40%
9
Comp off
0%
Comp off
0%
10
All off
0%
All off
0%
E
0
Comp off
0%
Comp off
0%
Analog input
1
11.0
40%
31.3
40%
2
9.8
45%
33.3
45%
3
9.0
50%
34.5
50%
4
7.2
60%
37.5
60%
5
5.9
70%
40.4
70%
6
5.0
80%
43.1
80%
7
4.1
90%
45.6
90%
8
3.1
100%
48.1
100%
9
3.1
48.1
10
3.1
48.1