Fan operation in the cooling
mode and thermal off con-
ditions.
00: Fan speed -Low
01: Fan OFF
02: Fan speed setting value
36
Use Primary Heater control 00: Cancel primary heater control
01: use primary heater control
38
Air conditioner Fan operation
interlocked with ventilation
00: air-conditioner fan operate very low
01: air-conditioner fan off
39
Indoor unit Auto-Start set-
ting
00: Use indoor unit auto restart
01: not use indoor unit auto restart
40
Occupy sensor ‘occupy
maintain’ time setting
00: 0 minute
01: 10 minutes
02: 30 minutes
03: 60 minutes
41
Simple Dry
Contact Setting
00: Default
01: Not Use Simple Dry Contact
02: Use Simple Dry Contact
03: Use for digital input
Some contents may not be displayed depending on the product function
Installer Setting Code Table
<General air conditioner product code table>
Code
Function
Value
01
Test run
01 : Set
02
Address Setting
00~FF : Address
03
E.S.P. Value
<ESP Step>
<ESP Value>
<Example>
01:VeryLow
0 ~ 255
02:Low
03:Med
04:High
05:Very High
04
Thermistor
01 : Remote control, 02 : Indoor unit, 03 : 2TH
05
Ceiling Height
01 : Low, 02 : Med, 03 : High, 04 : Very High
06
Static Pressure
01 : V-H, 02 : F-H, 03 : V-L, 04 : F-L
07
Master Setting
00 : Slave
If only “Plus1” series models 01 : Master
00 : Group setting
01 : Single setting
08
Override Setting
00 : Slave, 01 : master
09
Dry Contact
00 : Auto-Off, 01: Auto-On
10
Release 3 Min. Delay
01 : Set
11
Zone State
01 : Variable, 02 : Fixed
12
Celsius Fahrenheit Switching 00 : Celsius, 01:Fahrenheit (Optimized only for U.S.A)
13
Zone Type
00 : Zone Controller, 01:Damper Controller
14
Zone Number
02~04(Zone number)
17
Centigrade Control Settings 00 : 1 °C Control , 01 : 0.5 °C Control
18
Emergency Heater Setting
19
Function Setting for Group Control 01 : Not in use, 02 : In use
20
Plasma
00: Not Installed
01: Installed
21
Electric heater
22
Humidifier
23
Elevation Grill
24
Ventilation Kit
25
Auxiliary Heater
00: Not Installer
01: Installed-Normal
02: Installed-Duct type
26
Indoor unit address checking 00: Not Installed, 01: Installed
29
Settings for Refrigerant
Leak Detector Installation
00: Not Installed, 01: Installed
32
Static Pressure step
00: use static pressure (code 06) set value
01~11: static pressure step (code 32) set value
Function Code
ESP value
ESP step
Select mode
Setup Low Ambient
Setup FAN
Heating Operation
Speed
00 : not use
00 : not use
0 : fan off
01 : use
01~03: Setting step
1 : fan on
01~15 : Setting step
(step expand indoor unit)