4.0
Ton
Outdoor
Unit
Performance:
Cooling
Mode:
Capacity
(Btu/h)
48,000
Capacity
(tons)
4.0
Power
Input
(kW)
5.1
EER
9.50
Heating
Mode:
Power
Input
(kW)
5.3
Cooling
Nominal
Test
Conditions:
Heating
Nominal
Test
Conditions:
Indoor:
80
˚
F
DB
/67
˚
F
WB
Outdoor:
95
˚
DB
Indoor:
70
˚
F
DB
Outdoor:
47
˚
F
DB
/43
˚
F
WB
Electrical:
Power
Supply
(V/Hz/Ph)
208
‐
230/60/1
MOP
(A)
55
MCA
(A)
33
Rated
Amps
(A)
25.8
Compressor
(A)
24.8
Fan
Motor
(A)
1.0
Max
Starting
Current
(A)
‐
Operating
Range:
Cooling
(
˚
F
DB)
23
‐
118
Heating
(
˚
F
WB)
‐
4
‐
60
Notes:
Unit
Data:
Refrigerant
Type
R410A
Refrigerant
Control
EEV
Net
Unit
Weight
(lbs)
234
Heat
Exchanger
Coating
GoldFin™
Compressor:
Fan:
Quantity
2
Air
Flow
Rate
(CFM)
3,885
Piping:
Refrigerant:
Refrigerant
Charge
(lbs)
6.6
Standard
Features:
•
Limited
Warranty
with
LG
Certified
Installation
•
Two
Year
Functional
Parts
Warranty
•
Additional
Four
Year
Compressor
Warranty
•
Night
Quiet
Operation
•
Fault
Detect
and
Diagnosis
LG
Electronics
USA,
Inc.
1000
Sylvan
Ave,
Englewood
Cliffs,
NJ
07632/www.lg.com/us/
For
continual
product
development,
LG
reserves
the
right
to
change
specifications
without
notice.
Page
1
of
2
SEER
15.20
Vapor
Line
(in,
OD)
5/8
Braze
VRF
‐
SB
‐
BB
‐
002
‐
US
011D21
1.The
combina on
ra o
must
be
between
50
‐
130%.
2.Sound
pressure
levels
are
tested
in
an
anechoic
chamber
under
Korea
Standard
KSA0701.
3.All
communica on
cable
to
be
minimum
18
AWG,
2
‐
conductor,
stranded,
shielded
and
must
comply
with
applicable
local
and
national
code.
4.All
communica on
cable
to
be
minimum
18
AWG,
2
‐
conductor,
stranded
and
must
comply
with
applicable
local
and
national
code.
5.The
data
men oned
in
the
above
tables
is
applied
with
non
‐
ducted
indoor
units.
6.This
data
is
rated
0
above
sea
level,
with
25
of
refrigerant
line
per
indoor
unit
and
a
0
level
difference
between
outdoor
and
indoor
units.
All
capacities
are
net
with
a
combination
ratio
between
95
–
105%.
7.The
voltage
tolerance
is
±
10%.
8.Power
wiring
cable
size
must
comply
with
the
applicable
local
and
na onal
code.
9.Must
follow
installa on
instruc ons
in
the
applicable
LG
installa on
manual.
Capacity
(Btu/h)
53,500
Date:
Job
Name/Location:
PO
No.:
Architect:
Engr:
GC:
Rep:
For:
File
Approval
Mech:
Resubmit
Other
(Company)
(Project
Manager)
Tag
#:
ARUN047GS2
Multi
V™
Mini
Inverter
Rotary
Quantity
1
Oil
/
Type
PVE/FV50S
Type
Propeller
Fan
Motor/Drive
Brushless
Digitally
Controlled/Direct
Liquid
Line
(in,
OD)
3/8
Braze
Communication
Cable
(No.
x
AWG)
HSPF
9.20
Max
Num
of
Indoor
Units¹
8
Sound
Pressure²
dB(A)
(CLG/HTG)
51/53
Outdoor
to
Indoor³
2
x
18
Outdoor
to
Outdoor
⁴
2
x
18
Shipping
Weight
(lbs)
258