GENERAL DATA
Electrical
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded
down to the nearest standard fuse size.
Table 3: Vertical Air Handling Unit ODU Electrical Data.
Electrical Data
Nominal
Tons
Model
Name
Unit
Power Supply
Compressor
Quantity
Compres-
sor
Motor RLA
(Cooling)
Condenser Fan Motor(s)
Hz
Volts
Voltage
Range
MCA
MOP
Condenser
Fan Quan-
tity.
Condenser
Fan
Motor FLA
1.5
LUU189HV
60
208/230 Min.: 187
Max.: 253
20
30
1
13.5
1
1.6
2.0
LUU249HV
20
30
1
13.5
1
1.6
3.0
LUU369HV
32
40
1
22.0
2
1.6 x 2
3.5
LUU428HV
32
40
1
21.0
2
1.6 x 2
4.0
LUU488HV
32
40
1
21.0
2
1.6 x 2
Содержание LV181HV4