background image

9. Remove the nut, lock washer and flat

washer from heater terminal posts marked
L1, L2 and L3.

10. Connect wiring from control box panel to

the correct terminal post as shown on
heaterʼs wiring diagram.

Note:

The correct sequence for replacing the

hardware on the heater terminal posts is: 1)
wire connector 2) flat washer 3) locking washer
4) nut. “DO NOT OVER TIGHTEN NUT ON
TERMINALS” use a nut driver only to tighten
connection.(See Figure 6.)

4

L3

L2

Figure 6

Control Wiring

11. Connect control wires(Brown) on terminal

block (and P.C.B) as shown on wiring
diagram attached on compressor access
panel.

Power Wiring

12. Then route wires down through the

opening in the top of control box. Connect
wires to high voltage terminal block. Refer
to wiring diagram supplied with heater.

13. Check to make certain the proper size

fuses are installed per the fuse table for
the exact heater being used.

14. Ground unit at the grounding lug

provided. Make sure all field wiring
complies with all applicable codes and
water tightness.(Figure 7)

15. Remove compressor panel, then remove

unitʼs control box cover. Connect high
voltage leads to bottom of compressor
contactor or terminal block.(See unitʼs
wiring diagram.) Replace control box
cover and access panel onto unit.
(Figure 7)

CAUTION: 

Use copper conductors only to

prevent equipment damage. Unit terminals
are not designed to accept any other wiring.

16. Replace control box cover using four(4)

screws.

17. Replace heater access panel.

CAUTION:

Do not over tighten the nuts on the

heater terminals. if the nuts are over tightened
the ceramic insulators will break and heaters
must be replaced.

Maximum torque on nuts is 11 inch
pounds.

To Unit Control Box

Ground

Power Supply

Terminal Block

Figure 7

Содержание LKAEH098

Страница 1: ...UCTIONS Models LKAEH098 LKAEH188 LKAEH368 LKAEH368L Please read this instruction sheet completely before installing the product Installation work must be performed in accordance with national wiring standards by authorized personnel only P No 3828A30038F ...

Страница 2: ...4 60 60 60 60 80 80 60 60 80 80 100 100 125 125 150 150 150 150 60 60 60 60 80 80 60 60 80 80 100 100 125 125 150 150 150 150 Heater Rated Volts Standard indoor fan motor M C A M C A M F S M F S M C B M C B Oversized indoor motor Note Heater KW ratings are at 380 415V for 380 415V unit M C A Minimum Circuit Ampere M F S Maximum Fuse Size M C B Maximum Circuit Breaker HACR type Circuit Breaker per ...

Страница 3: ...ater control assembly of heater cavity using four 4 screws See Figure 4 Important Make sure the heater arm slides into heaterʼs back support bracket Two Bank Heaters Installation LKAEH368 7 For two heaters installation align holes and secure screws to the control box as shown in Figure 3 8 Secure the heater control assembly on heater cavity using four 4 screws See Figure 5 Important Make sure the ...

Страница 4: ...th heater 13 Check to make certain the proper size fuses are installed per the fuse table for the exact heater being used 14 Ground unit at the grounding lug provided Make sure all field wiring complies with all applicable codes and water tightness Figure 7 15 Remove compressor panel then remove unitʼs control box cover Connect high voltage leads to bottom of compressor contactor or terminal block...

Отзывы: