background image

2

Table 1 Accessory Heaters Electrical Data

Ton

6.25/7.5RT

8.5/10/12.5RT

15/17.5RT

20/25RT

Heater

Model No.

Heater

KW Rating

Control

Stages

26.0/27.2
37.5/39.5
60.5/64.5
42.0/43.2
53.5/55.5
76.5/80.5

79.4/95.3

100.2/120.3

108.6/130.4

380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3
380-415/50/3

380-415/50/3

LKAEH098
LKAEH188
LKAEH368
LKAEH098
LKAEH188
LKAEH368
LKAEH188
LKAEH368

LKAEH368L

7.5/9.0

15.1/18.0
30.2/36.0

7.5/9.0

15.1/18.0
30.2/36.0
15.1/18.0
30.2/36.0

30.2/36.0

1
1
2
1
1
2
1
2

2

60/60
60/60
80/80
60/60
70/70

100/100
125/125
150/150

150/150

60/60
60/60
80/80
60/60
70/70

100/100
125/125
150/150

150/150

31.0/32.2
42.5/44.5
65.5/69.5
47.0/48.2
58.5/60.5
81.5/85.5

85.4/101.3

106.2/126.3

114.6/136.4

60/60
60/60
80/80
60/60
80/80

100/100
125/125
150/150

150/150

60/60
60/60
80/80
60/60
80/80

100/100
125/125
150/150

150/150

Heater

Rated Volts

Standard indoor fan motor

M.C.A

M.C.A

M.F.S

M.F.S

M.C.B

M.C.B

Oversized indoor motor

Note:

Heater KW ratings are at 380/415V for 380/415V unit.
M.C.A; Minimum Circuit Ampere
M.F.S; Maximum Fuse Size
M.C.B; Maximum Circuit Breaker
* HACR type Circuit Breaker per NEC.

Installation

1. Loosen the screw that secures heater

compartment access panel. Lift up, pull
towards you and slide it down to remove.

2. Remove four(4) screws from block off panel

to expose heater cavity and heaterʼs back
support bracket. Save screws for installing
heater later.(See Figure 2.)

Heater Access Panel

Compressor Access Panel

Figure 1

Figure 2

: Open and lock unit disconnect

switch before installing this accessory to prevent
injury or death due to electrical shock or contact
with moving parts.

WARNING

Support

Bracket

Block off panel

Heater Cavity

Содержание LKAEH098

Страница 1: ...UCTIONS Models LKAEH098 LKAEH188 LKAEH368 LKAEH368L Please read this instruction sheet completely before installing the product Installation work must be performed in accordance with national wiring standards by authorized personnel only P No 3828A30038F ...

Страница 2: ...4 60 60 60 60 80 80 60 60 80 80 100 100 125 125 150 150 150 150 60 60 60 60 80 80 60 60 80 80 100 100 125 125 150 150 150 150 Heater Rated Volts Standard indoor fan motor M C A M C A M F S M F S M C B M C B Oversized indoor motor Note Heater KW ratings are at 380 415V for 380 415V unit M C A Minimum Circuit Ampere M F S Maximum Fuse Size M C B Maximum Circuit Breaker HACR type Circuit Breaker per ...

Страница 3: ...ater control assembly of heater cavity using four 4 screws See Figure 4 Important Make sure the heater arm slides into heaterʼs back support bracket Two Bank Heaters Installation LKAEH368 7 For two heaters installation align holes and secure screws to the control box as shown in Figure 3 8 Secure the heater control assembly on heater cavity using four 4 screws See Figure 5 Important Make sure the ...

Страница 4: ...th heater 13 Check to make certain the proper size fuses are installed per the fuse table for the exact heater being used 14 Ground unit at the grounding lug provided Make sure all field wiring complies with all applicable codes and water tightness Figure 7 15 Remove compressor panel then remove unitʼs control box cover Connect high voltage leads to bottom of compressor contactor or terminal block...

Отзывы: