WIRING
ENGLISH
3
7
The position of the fixing screws
Yellow
1 Put the installation paper on the place and
determine the position and height of the
fixing screws of the deluxe wired remote
controller.
- Refer to the printed side of the installation
paper.
2 Please connect indoor unit and
remote controller using connec-
tion cable.
- The product is being shipped
with the cable connected only to
the remote controller. Put each
cable to the remote controller
according to the color match
- Please use extension cable if the
distance between wired remote
controller and indoor unit is more
than 10m.
Main frame
CN-REMO
LO2K
J15
LO
1K
LO
1D
C0
7D
C0
1K
J14
CN-DISP
CN-M
CN-
ZONE
C
IC0
1A
Be careful not to alter the
colors of the remote
controller connection cables.
Brown
Red
Yellow
Yellow
Yellow
Yellow
Please check if connector is normally connected.
Connecting cable
Indoor
Unit side
CAUTION
Installation work must be performed in accordance with the national wiring standards by
authorized personnel only.
• Installations must comply with the applicable local/national or international standards.
• Apply totally enclosed noncombustible conduit (metal raceway) in case of local electric &
building code require plenum cable usage.
• When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
• Do not install the remote controller near by window or door, because it is difficult to sens-
ing real room temperature.
• Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of
the remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be con-
nected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
!
12V
Red
Signal
Yellow
GND
Black
Wired remote controller installation
Содержание B70AWYN985
Страница 54: ......