WIRING
ENGLISH
Communication and Power
wiring cable
1) Communication wiring cable
- Types : shielding wire
- Cross section : 1.0~1.5mm
2
- Maximum allowable temperature: 105°C
- Maximum allowable line length: under
100m
2) Remote wiring cable
- Types : 3 wiring cable
4) Separation of transmission and power lines
- communication and power wiring cable
are run alongside each other then there is
a strong likelihood of operational faults
developing due to interference in the sig-
nal wiring caused by electrostatic and elec-
tromagnetic coupling.
The tables below indicates our recommen-
dation as to appropriate spacing of com-
munication and power wiring cable where
these are to be run side by side
Current capacity of
power line
Spacing
100V or
more
10A
300mm
50A
500mm
100A
1000mm
Exceed
100A
1500mm
NOTE
!
• The figures are based on assumed
length of parallel cabling up to 100m.
For length in excess of 100m the fig-
ures will have to be recalculated in
direct proportion to the additional length
of line involved.
• If the power supply waveform contin-
ues to exhibit some distortion the rec-
ommended spacing in the table should
be increased.
- If the lines are laid inside conduits then
the following point must also be taken
into account when grouping various
lines together for introduction into the
conduits
- Power lines(including power supply to
air conditioner) and signal lines must
not be laid inside the same