
46
Room Air Conditioner
Troubleshooting Guide
Evacuation
(All amount of refrigerant leaked)
• Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
OPEN
CAUTION:
Use vacuum pump equipped with check value
applied to be prevented from flowing back-
ward.
Содержание AS-H076QGA2/QNA2
Страница 31: ...Service Manual 31 Remote Control Operations The remote control transmits the signals to the system Operation ...
Страница 36: ...36 Room Air Conditioner Schematic Diagram HVB TYPE PLASMA ...
Страница 40: ...40 Room Air Conditioner Schematic Diagram DISPLAY ASSEMBLY 6871A20476 6871A90476 TOP VIEW BOTTOM VIEW ...
Страница 68: ...P No 3828A20462A Printed in Korea ...