Installation
Voltage
Measure the voltage at the terminal block using a voltmeter.
ON
OFF
CON
NEC
TION
KIT
1. Make sure that the circuit breaker
switch is put in the
OFF
position, and
then measure the voltage. If the volt-
age is higher than 0 V, do not use the
battery pack. Contact LG Chem or
your distributor.
2. Move the circuit breaker switch to the
ON
position, and then measure the
voltage. If the voltage is lower than
38 V, do not use the battery pack. Con-
tact LG Chem or your distributor.
3.10 Connecting the battery pack to the inverter
WARNING
Make sure that the inverter is turned off before connecting the battery pack
to the inverter.
ON
OFF
CON
NEC
TION
KIT
Before connecting the battery pack to the
inverter, make sure that the circuit breaker
switch is in the
OFF
or Trip position.
21