5
300802431_002_C0 - 09/2019 - © Leybold
2 Profibus
GSD file
The GSD file and the manual can be downloaded from
www.leybold.com -> Downloads -> Download Software -> PC software for
DRYVAC and RUVAC WH pumps.
The GSD file for the versions in this manual is different from the GSD file for
the DRYVAC-i versions. Do not mix them up.
2.1 Parameter Settings
No.
Name
Description
Leybold Setting
b1-01 Frequency Reference Selection *1 *2
Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
3
b1-02 Run Command Selection *1 *2
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB
3
F6-30 Node Address *3
0 to 125
6
F6-31 Clear Mode Selection
Selects the action to take when a „Clear Mode“
command is received
0: Resets back to 0
1: Maintains the previous value
0
F6-32 PROFIBUS Map Selection
0: PPO Type
1: Conventional
1
* 1. To start and stop the drive through the PROFIBUS-DP network, set b1-02 to “3”. To control the frequency reference of the drive via the
PROFIBUS-DP network, set b1-01 to “3”.
* 2. When b1-01 = 3 and/or b1-02 = 3 are selected and the communication option is not installed, V1000 detects oPE07 instead of oPE05 with
software version 1010.
* 3. All node addresses must be unique. Node addresses 0, 1, and 2 are typically reserved for control, maintenance, and diagnostic equipment. The
ERR light will illuminate when 0 or greater than 125 is entered.
MEMOBUS/Modbus Message
MEMOBUS/Modbus Message is
not
active.