7.
System Menus
7.1
Fault Accept
Before accepting faults, the fault must be noted in the log book, along with the time the fault was
reported.
To accept the fault, enter either the access level 2 (code: 1664) or access level 3 (code: 1812) menu,
then press zone button 1. The buzzer will silence and the general fault LED will now go steady.
Press zone button 8 to exit this menu and to return to the menu options.
The buzzer will resound on each new fault.
7.2
Panel Indicator Test
To test the panel indicators, enter either the access level 2 (code: 1664) or access level 3 (code: 1812)
menu, then press zone button 2.
All LEDs will illuminate in a predefined sequence, and the buzzer will sound.
Press zone button 8 to stop the panel indicator test and to return to the menu options.
7.3
Extended Fault Menu
Enter the access level 2 code (1664) or access level 3 (code: 1812) then press zone button 3.
Zone Indicator Status
Description
1-4
Blank
Line card configured as not fitted
Yellow Solid
Line card configured as fitted but not present
Green Solid
Line card configured as fitted and present
5
Blank
Net In not configured
Green Solid
Net In healthy
Yellow Flashing
Net In fault
6
Blank
Net Out not configured
Green Solid
Net Out healthy
Yellow Flashing
Net Out fault
7
Green Solid
Display Processor Healthy
Yellow Solid
Display Processor Fault
8
Green Solid
Exchange Processor Healthy
Yellow Solid
Exchange Processor Fault
7.4
Line Identify
Line identify is a helpful feature to prove that the line numbers are correct i.e. that line 1 is connected
to line 1 terminals. It does this by activating the ringer tone on the outstation with the number of rings
corresponding to the line number, i.e. line 2 will activate the outstation with 2 rings in this mode.
Enter the access level 3 engineer code (1812) then press zone button 4. The lines for the fitted Line
Cards will have their corresponding zone lights illuminated flashing magenta, e.g. if there are 2 line
cards fitted, then zones 1-4 will be flashing.
Visit each outstation in turn and listen to the number of rings to confirm they have the correct
configuration. Press the call button on each outstation to acknowledge.
For example:
•
Visit outstation for line 1. This should be ringing once. Press the call button to acknowledge.
Listen for the cadence tone, then press the cancel button.
•
Visit outstation for line 2. This should be ringing twice, again press the call button to
acknowledge. Listen for the cadence tone, then press the cancel button.
When you return to the Master Station, the outstation lines that have been acknowledged will be
illuminated solid magenta.
Press zone button 8 to stop the line identify test and to return to the menu options.
Note: This feature does not work with “Assist Call” as there is no ringer present.