background image

Single Pole (One location) or 3-Way (Multi-location)

Electronic Switch 

Cat. No. VZS15-1L, Lighted

Incandescent-1800W – Magnetic low-Voltage-1800VA (1440W)

Electronic Low-Voltage-1800W – Fluorescent-1800VA – Supplemental-1/2 HP

120VAC, 60Hz

INSTALLATION INSTRUCTIONS

WARNINGS AND CAUTIONS

:

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.

•  If you are unsure about any part of these instructions, consult a qualified electrician.

•  Vizia™ electronic switches are not compatible with standard 3-way or 4-way switches. They must be used with compatible Vizia™ on/off remotes.

•  Recommended minimum wall box depth is 2-1/2”.

WARNINGS AND CAUTIONS

:

•    Use only one (1) Vizia

TM

 electronic switch in a multi-location circuit with up to 9 coordinating remotes without LEDs or up to 4 matching remotes with LEDs.

•  Maximum wire length from dimmer to all installed remotes cannot exceed 300 ft (90 m).

•  Disconnect power at circuit breaker or fuse when servicing, installing or removing fixture.

•  Use this device only with copper or copper clad wire. With aluminum wire use only devices marked CO/ALR or CU/AL.

IMPORTANT :

 For 3-Way applications, note that one of the screw terminals 

from the old switch being removed will usually be a different color (Black) 

or labeled Common. Tag that wire with electrical tape and identify as the 

common (Line or Load) in both the switch wall box and remote wall box.

DI-000-VZS15-02A-X3

 Tools needed to install your Switch:

Slotted/Phillips Screwdriver 

Electrical Tape 

Pliers 

 

Pencil 

 

 

Cutters 

 

Ruler

Hot (Black)

Neutral (White)

Load

Switch

BK

WH

Black

White

RD

Green

Ground

YL/RD

Line 

120VAC, 60Hz

Use Terminal for 3-Way or

More Applications Only.

For Single-Pole Applications,

Do Not Remove This Label.

WIRING SWITCH:

Connect wires per WIRING DIAGRAM as follows:

•  Green or bare copper wire in wall box to Green terminal screw.

•  Line Hot wall box wire to terminal screw marked "BK".

•  Load wall box wire to terminal screw marked "RD".

•  Line Neutral wall box wire to terminal screw marked "WH".

•  Switch terminal screw marked "YL/RD" should have Red insulation 

label affixed. 

 

NOTE:

 If insulating label is not affixed to terminal screw marked "YL/RD", 

use electrical tape to cover.

• 

Proceed to Step 5.

Hot (Black)

Neutral (White)

Coordinating Remote (no LED)

YL/RD

YL/RD

RD

WH

RD

BK

Black

BK

WH

White

Line 

120VAC, 60Hz

Green

Ground

Green

Ground

(unused)

(unused)

Load

Switch

WIRING SWITCH:

Connect wires per WIRING DIAGRAM as follows:

NOTE:

 The switch must be installed in a wall box that has a Line Hot 

connection.

NOTE:

 Maximum wire length from switch to all installed remotes 

cannot exceed 300 ft (90 m).

•  Green or bare copper wire in wall box to Green terminal screw.

•  Line Hot (common) wall box wire identified (tagged) when 

removing old switch

  to terminal screw marked "BK".

•  First Traveler wall box wire to terminal screw marked "RD" 

(note wire color)

.

•  Remove Red insulating label from terminal screw marked "YL/RD".

•  Second Traveler wall box wire to terminal screw marked "YL/RD"  

(note wire color)

. This traveler from the switch must go to the 

terminal screw on the remote marked "YL/RD".

•  Line Neutral wall box wire to terminal screw marked "WH".

WIRING COORDINATING REMOTE:

Connect wires per WIRING DIAGRAM as follows:

NOTE:

 "BK" and "RD" terminals on coordinating remote are unused.

Tighten both screws.

NOTE:

 Maximum wire length from switch to last remote is 

300 ft (90 m).

•  Green or bare copper wire in wall box to Green terminal screw.

•  Load wall box wire identified (tagged) when removing old switch to 

First Traveler 

(note color as above)

.

•  Second Traveler wall box wire 

(note color as above)

 to terminal 

screw marked  "YL/RD". This traveler from the remote must go to 

the terminal screw on the switch marked "YL/RD".

•  Remove White insulating label from terminal screw marked "WH". 

•  Line Neutral wall box wire to terminal screw marked "WH". 

•  Proceed to Step 5.

INSTALLING YOUR SWITCH

NOTE:

 Use check boxes        when Steps are completed.

Changing the color of your Switch:

Your switch includes three color options. The switch ships with the White 

frame attached. To change color of frame, proceed as follows:

Line up tabs and 

press in side to attach

Push in side 

at tab to release

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

��

���

WARNING: 

TO AVOID FIRE SHOCK OR DEATH; TURN 

OFF POWER 

at circuit breaker or fuse and test that power is 

off before wiring!

 

Step 1

2

4

3

1

2

4

1

5

3

Single Pole
1.

 Line (Hot)

2.

 Neutral

3.

 Ground

4.

 Load 

3-Way
1.

 Line or Load 

(see important instruction below)

2.

 Neutral

3.

 Ground

4.

 First Traveler – note color

5.

 Second Traveler – note color. 

NOTE:

 For 

matching remote w/LEDs installation, the 

First Traveler

 becomes Line Hot.

Identifying your wiring application (most common):

NOTE:

 If the wiring in your wall box does not resemble any of 

these configurations, consult a qualified electrician.

 

Step 2

 

Step 3

BK

WH

YL/RD RD

Terminal

Screw marked

Black (BK)

Terminal

Screw marked

Red (RD)

Terminal

Screw marked

Yellow/Red

(YL/RD)

Terminal Label:

Use Terminal for 3-Way or More Applications Only.

For Single-Pole Applications, Do Not Remove This

Label.

4

3

2

Terminal

Screw marked

White (WH)

1

Single Pole Wiring Application:

 

Step 4a

 

Step 4a cont'd

BK

WH

YL/RD RD

Coordinating Remote

Switch

5

2

1

4

3

BK

WH

YL/RD RD

4

3

1

5

Terminal

Screw marked

Red (RD)

Terminal

Screw marked

White (WH)

2

Terminal

Screw marked

Black (BK)

Terminal

Screw marked

Yellow/Red

(YL/RD)

3-Way Wiring with Coordinating Remote 

(no LED) Application:

 

Step 4b

Preparing and connecting wires:

This switch can be wired using side wire terminal screws or 

through backwire openings. Choose appropriate wire stripping 

specifications accordingly.

•  Make sure that the ends of the wires from the wall box are 

straight (cut if necessary).

•  Remove insulation from each wire in the wall box as shown.

•  For Single-Pole Application, go to Step 4a.
•  For 3-Way Coordinating Remote (no LEDs) Application, go to Step 4b.
•  For 3-Way Matching Remote (with LEDs) Application, go to Step 4c.

5/8" 

(1.6 cm)

Strip Gage 

(measure bare 

wire here)

Cut 

(if necessary)

Side Wire Connection 

Side wire terminals accept #14 

AWG 

solid wire copper only

.

Back Wire (either hole may be used) 

Back wire openings use #14-12 AWG 

solid wire copper only

 

Step 4b cont'd

Отзывы: