Occupancy Sensor AutoON/Override Power Pack

Cat. No. OSP20-RxH

Load Ratings:

 20A, 2400W @ 120V, 60Hz - Incandescent / 20A, 2400VA @ 120V, 60Hz - Fluorescent

20A, 5540VA @ 277V, 60Hz - Fluorescent / 1/2 HP @ 120V - Motor Load / 2 HP @ 240/277V, 60Hz - Motor Load / 0.5A 120V, 1A 30VDC - HVAC Relay

For use with OSCxx, OSWxx, ODCxx, and ODWxx Occupancy Sensors

INSTALLATION INSTRUCTIONS

WARNINGS AND CAUTIONS:

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.
•  If you are unsure about any part of these instructions, consult an electrician.
•  Use this device with 

copper or copper clad wire only

.

•  Disconnect power when servicing fixture or changing lamps.

DI-000-OSP20-00A

• Lights 

Flickering

 

-  Lamp has a bad connection.

 

-  Wires not secured firmly with wire connectors.

•  Lights did not turn ON

 

-  Circuit breaker or fuse has tripped.

 

-  Lamp is burned out.

 

-  Lamp Neutral connection is not wired.

 

-  Hold OFF or Manual ON input is active.

 

-  Low Voltage miss wired. Verify wiring pre appropriate diagram.

 

-  Line Voltage miss wired. Verify wiring pre appropriate diagram.

•  Lights stay ON

 -  

Constant motion. 

To Test:

 adjust sensor; remove motion source (HVAC, Mask, or 

move sensor). 

•  Lights turn ON too long

 

-  Adjust sensor settings.

•  Lights came ON during presentation

 

-  AutoON mode is connected and the time delay expired.

 

-  Increase the sensor time delay or generate more motion during the presentation.

•  Lights do not turn OFF with time delay

 

-  Hold ON input is active.

 FEATURES

•  Title 24 Compliant
•  Hold On/ Hold Off capabilities
•  Regulated 24VDC, 150mA output current 
•  Mounts inside Fluorescent Ballast cavity
•  Mounts inside or outside Junction Box
•  Rated for Plenum spaces

 RATINGS

Part Number

 

HVAC Relay 

Power Input

1

  

Power 

Output

2

OSP20-RxH  

Yes  

120-277VAC, 50/60Hz 

24VDC, 150mA 3.6W

1

 Input voltage tolerance 10%, Frequency tolerance 5%.

2

 Output voltage tolerance 15%, Output voltage listed at nominal.

 DESCRIPTION 

The power pack contains a power supply, a load switching relay and an HVAC relay. 
The power supply provides Class II low-voltage power for OSCxx, OSWxx, ODCxx, 
andODWxx Series Occupancy Sensors. The OSP power packs can also supply 
power to the OSA20, Add-A-Relay. The relay in the power pack is controlled by the 
occupancy sensors connected via the 22 Gauge Blue "occupancy" wire. Multiple 
occupancy sensors can be connected to a single power pack in order to fully cover an 
area. The power packs include zero cross switching circuitry to minimize inrush current 
associated with incandescent and electronic ballasts. This reduces wear and tear on 
the relay contacts making the power pack last longer.

Application Notes:

Loads that exceed the ratings of a single power pack can be connected to an Add-
A-Relay, which is powered from the low-voltage output of the power pack (OSPxx). 
The Add-A-Relay contains the load switching and HVAC relays and is powered by an 
OSPxx Power Pack.

1.

  When a lighting load exceeds a single power pack’s rating, the load can be split 

between multiple power packs. The low voltage occupancy input (Blue wire) and DC 
return (Black wires) of the power packs must be connected together for all power 
packs to operate together as one. Connect the Blue (occupancy) wires of all power 
packs and sensors together. Connect the Black (return) wires of all power packs and 
sensors together. Connect the Red (+24VDC) wires of the sensors to the Red wires 
of only one power pack. Never connect the Red (+24VDC) wires of two different 
power packs together.

2.

  When more sensors are required than one power pack can supply, multiple power 

packs can be used to supply power to the occupancy sensor, but not switch any 
load. The primary power pack is the power pack switching the load. The secondary 
power packs only provide low voltage power to the occupancy sensor(s). Connect 
as many sensors to the primary power pack as possible (see current capacity 
section below), by connecting the Red wires of the sensors to the Red wire 
(+24VDC) of the primary power pack. Connect the Red wires (+24VDC) of the 
remaining sensors to the Red wires of the secondary power pack. Connect the 
Black (return) wires of all power packs and all sensors together. Connect the Blue 
(occupancy) wire of all sensors together to the Blue wire (occupancy) of the primary 
power pack. Never connect the Red (+24VDC) wires of two different power packs 
together.

FCC COMPLIANCE STATEMENT (OSP20 Only)

This equipment has been tested and found to comply with the limits for a Class A digital 
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide 
reasonable protection against harmful interference when the equipment is operated 
in a commercial environment. This equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this 
equipment in a residential area is likely to cause harmful interference in which case the 
user will be required to correct the interference at his own expense.

 LOW-VOLTAGE CURRENT CAPACITY

NOTE:

 Add-a-Relay current consumption = 50mA per unit.

 INSTALLATION

OSP20

Total Number of S Total Number of Add-a-Relays ≤ 150mA

1.

 

WARNING:

 TO AVOID FIRE, SHOCK, OR DEATH; 

TURN OFF POWER

 AT 

CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!

2.

 

Mount power pack per desired application:

 

A.

   To mount outside 4"x4" junction box using 2" EMT nipple, refer to 

Figure 1

. Wire 

per instructions 

Step 3A

 and 

3B

.

 

B.

   To mount inside 4"x4" junction box, refer to 

Figure 2

. Wire per instructions 

Step 

3A

 and 

3B

.

 

 

• Ensure that conduit/cable entry clamp is located in corner of junction box.

 

 

• Dress wires to provide enough clearance when device is installed.

 

 

 

CAUTION:

 Low-voltage wires must also be dressed so they are separate 

from the high voltage (Class I) conductors. Refer to local building codes for the 
appropriate installation requirements for the low voltage wiring. Jacketing over the 
low-voltage wires may be required to provide appropriate insulation from the high-
voltage wiring.

 

C.

   To mount inside ballast cavity of light fixture, refer to 

Figure 3A

. Wire per 

instructions 

Step 3A and 3B

.

 

 

 

CAUTION:

 Low-voltage wires must also be dressed so they are separate 

from the high voltage (Class I) conductors. Refer to local building codes for the 
appropriate installation requirements for the low voltage wiring. Jacketing over the 
low-voltage wires may be required to provide appropriate insulation from the high-
voltage wiring.

 

D.

   To mount outside ballast cavity of light fixture, refer to 

Figure 3B

. Wire per 

instructions 

Step 3A

 and 

3B

.

3A.

 

Line Voltage Wiring:

 Remove 5/8" (1.6 cm) of insulation from each circuit conductor. 

Make sure that ends of conductors are straight. Connect lead wires from Power Pack 
to LINE circuit per appropriate WIRING DIAGRAM as follows: Twist strands of each 
lead tightly and, with circuit conductors push firmly into appropriate wire connector. 
Screw connectors on clockwise making sure that no bare conductor shows below the 
wire connectors. Secure each connector with electrical tape.

3B.

 

Class II and HVAC Wiring:

 Connect Low-Voltage wires from Power Pack to Sensor 

per appropriate WIRING DIAGRAM as follows: Twist strands of each lead tightly and, 
with circuit conductors, push firmly into appropriate wire connector. Screw connectors 
on clockwise making sure that no bare conductor shows below the wire connectors. 
Secure each connector with electrical tape.

4.

 Refer to sensor Installation Instructions for further details.

5.

 Restore power at circuit breaker or fuse. 

INSTALLATION IS COMPLETE

.

Mounts outside

junction box

Figure 1

Line Voltage Wires

Class II Wires

Figure 2

Mounts inside

junction box

Line Voltage Wires

Class II Wires

 OPERATION

The AutoOn/Override Power Pack can be turned ON and OFF automatically using an 
occupancy sensor input, a timer, panel or BAS input, and manually from an optional low 
voltage momentary switch.

AUTO ON (See Wiring Diagram):

The occupancy sensor input, Hold ON input and the optional momentary switch input can 
all be used to turn the load ON.
When the load is turned OFF using the momentary switch, the power pack does not turn 
it ON automatically until after the sensor time delay expires (e.g., presentation mode). 
Pressing the momentary switch before the sensor time delay expires turns the load ON.
When the occupancy sensor’s time delay expires, the power pack reverts to AutoON 
mode and it turns the load ON with the next input from the occupancy sensor.

MANUAL ON (See Wiring Diagram):

Occupants must press the low voltage momentary switch to turn the load ON.
When the occupancy sensor is the only input keeping the load ON, the load turns OFF 
when the sensor time delay expires. If the sensor input re-triggers within 30 seconds after 
the load turns OFF, the load turns ON again. After the 30 seconds expire with no sensor 
input press the momentary switch to turn the load ON.

LOW VOLTAGE INPUTS

24VDC input wires are provided to control the load relay. The inputs may be used in 
combination or individually, depending on the application(s). See wiring diagrams for 
connections.

MAINTAINED INPUTS
Occupancy Sensor (Blue)

 - This input is for occupancy sensor AutoON/AutoOFF.

Applying 24v closes the relay (Occupied). Remove the voltage and the relay opens (Vacant). 

Occupancy Sensor (Blue/White)

 - This input is for occupancy sensor ManualON/AutoOFF.

When the attached occupancy sensor detects motion, no action occurs. A local 
momentary switch is required to manually turn the load ON. Then the sensor will turn the 
load OFF when the time delay expires.  

Hold ON (Yellow)

 - This input is intended for timer or panel input.

Applying 24VDC closes the relay.  Remove the voltage and the relay opens if no other 
input is holding it closed. It overrides the Control ON input. 

Hold OFF (Orange)

 – This input is used for timer, panel, BAS or load shed input.

Applying 24VDC opens the relay.  Remove the voltage and the relay can accept any other 
input. It overrides the Control ON and Hold ON inputs.

Local Switch (Yellow/Orange)

 – This input is for a low voltage momentary switch.

Applying 24VDC momentary input changes the relay to the opposite state. It overrides the 
Control ON, Hold ON and Hold OFF inputs.

•  All wires rated at 105

o

 C, 600V insulation.

•  Class II wires are Teflon coated, for plenum applications.
•  HVAC wiring is Class I and Class II rated.

Line Voltage Wires

Class II Wires

Line 120-277V (OSP20-Rx0)

Neutral

Load

Load

Power (24 VDC)

DC Return

Occupancy Auto ON

HVAC Wires

HVAC Common

HVAC NO (Normally Open)

HVAC NC (Normally Closed)

Occupancy Manual ON

Hold ON

Hold OFF

Local Switch Input

Signal Name

Black

White

Blue

Blue

Red

Black

Blue

Green

Brown/White

Brown

Blue/White

Yellow

Orange

Yellow/Orange

Color

18 AWG

18 AWG

14 AWG

14 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

Gauge

Wire Designations

 TROUBLESHOTING

WEB 

VERSION