background image

 

 

 

February 28

th

 , 2013 

 

Models beginning with MO, MK, 7B, 6S, 6F or 5B 

The Mini Meter™

 

 

Product Description 

Technical Specifications 

Installation Instructions 

 

www.

.com

[email protected]

1.800.561.8187

Содержание Mini Meter

Страница 1: ...February 28th 2013 Models beginning with MO MK 7B 6S 6F or 5B The Mini Meter Product Description Technical Specifications Installation Instructions www com information itm com 1 800 561 8187...

Страница 2: ...l Display Information 7 3 Installation Instructions 8 3 1 Explanation of Warning Symbols 8 3 2 Safety Precautions 8 3 3 Preparation 9 3 4 List of Materials 9 3 5 Mounting the Enclosure 9 3 5 1 Mountin...

Страница 3: ...escription The Leviton Mini Meter is a self powered current transformer CT rated electronic kilowatthour kWh meter designed for permanent connection to an electrical service Mini Meters come in single...

Страница 4: ...y requirements set forth in ANSI C12 10 Certified to California Division of Measurement Standards Approved by the California Energy Commission for use in California Solar 1 4 Physical Description 1 4...

Страница 5: ...Installation Manual Leviton Manufacturing Co Inc 4 1 4 2 Enclosures Mini Meter and Epoxy Encapsulated module enclosures mounting drawings are shown below in figure 2 www com information itm com 1 800...

Страница 6: ...100 A models 0 11 A secondary for 0 1 A secondary models 0 22 A secondary for 0 2 A secondary models Line Frequency 50 60 Hz Power Factor Range 0 5 to 1 0 leading or lagging Accuracy 0 5 of registrat...

Страница 7: ...respect to neutral 7B and 5B models only CT Inputs CT1 X1 Current Transformer input CT1 Colored wire of CT 1 CT1 X2 Current Transformer input CT1 White wire of CT1 CT2 X1 Current Transformer input CT...

Страница 8: ...1000 For 12 VDC electro mechanical counter 12 VDC 12 VDC output current rating is 3 mA max MMS and MMD models only Table 2 I O connections Recommend Leviton mechanical counter 1 kWh models 0 1 kWh mod...

Страница 9: ...cuit and consult the operation manual 3 2 Safety Precautions WARNING Installation of electric meters requires working with possibly hazardous voltages These instructions are meant to be a supplement t...

Страница 10: ...d mounting material Line 1 Line 2 and Neutral hook up wires as needed for the electrical service Wires must be 18 AWG or larger and insulated for 300 VAC min Current Transformers CTs This product is d...

Страница 11: ...xercised to keep drill bit away from components inside the enclosure Type 4X conduit and fittings must be used in order to maintain the outdoor rating of the enclosure 3 5 3 Mounting Procedure and Con...

Страница 12: ...for wiring diagram 4 Route wires through the conduit if not already done 5 Trim the wire to the appropriate length to avoid coils of excess wiring 6 Strip wiring to approximately 300 inches if needed...

Страница 13: ...compress and weaken the conductor Current and voltage inputs must be installed in phase for accurate readings e g CT1 on Line 1 CT2 on Line 2 Leviton solid core CTs Installing solid core CTs 1 Route...

Страница 14: ...Mini Meter Installation Manual Leviton Manufacturing Co Inc 13 3 Phase 4 wire hookup diagram Leviton Leviton www com information itm com 1 800 561 8187...

Страница 15: ...ected to the meter in order for the reverse phase LED to function correctly If a proper load is connected and the LED is illuminated power down the voltage supply and verify that CTs are installed cor...

Страница 16: ...CT connections and orientations Make sure there is sufficient load to draw a significant current Test the voltage being supplied to the meter using an AC voltmeter 3 Registered consumption low Check...

Отзывы: