Wireless Intelligent Fixture Sensor and Controller 

1/2 in. KO, 0-10V and DALI

Cat. Nos. ZL07S, ZL0DS, ZL070, ZL0D0-N00

INSTALLATION INSTRUCTIONS

ENGLISH

PK-A3379-10-00-2A

Product Description

The Intellect™ Wireless Intelligent Fixture Sensor and Controller are 
wireless devices that integrate wireless control technology directly into 
lighting fixtures. The wireless devices are designed to be installed into a 
1/2 in. knock-out and interface to the driver via 0-10V or DALI, depending 
on the model. The wireless devices interface with Leviton’s wireless 
systems using its built-in radio. The wireless devices are designed to be 
powered from the driver and in the case of 0-10V, requires a dim-to-off 
driver to be used. The wireless devices may be installed into your fixture 
by the fixture manufacturer or may be added in the field if all requirements 
are met. When the wireless devices are pre-installed on a fixture, refer to 
fixture documentation for installation methods, means, and requirements.

WARNING

TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER 

at circuit breaker or fuse and test that power is off before wiring!

Installation

1.

   

 

Remove threaded lock nut.

2.

  

 

 

Secure wireless devices in knock-out by inserting until tabs are 
holding head firmly against fixture.

3.

   

 

Use lock nut to further secure sensor, if needed.

4.

   

 

Remove 4 to 5 mm of insulation from each circuit conductor.

5.

   

 

Make sure ends of conductor are straight.

6.

   

 

Push conductor firmly into appropriate wire connector.

7.

   

 If installing with Emergency Sense Module (ZL027-0ES):

 Connect 

the Emergency Sense Module to the Sensor using the cable included 
with the ZL027-0ES.

8.

   

 

Connect the Emergency Sense Module to normal power.

9.

   

 

Restore power at circuit breaker or fuse. 

10.

 

 

Proceed to device enrollment per the included sheet and 
configuration per your system requirements. Installation is complete.

Installation Requirements

•  Installation and servicing should always be performed by  

qualified personnel.

• 1/2 in. diameter knock-out free of excess material.
•  Dim-to-OFF LED driver with 12-24V AUX power supply and 0-10V or 

DALI control.

ZL070/ZL07S-N00

ZL0D0/ZL0DS-N00

Emergency Wiring

When used for emergency lighting, the ZL027-0ES Emergency Sense 
Module is required and shall be connected using the supplied cable. 
The control input wires for the emergency light fixture are connected 
to emergency power, and the Emergency Sense Module is connected 
to normal power. Upon loss of normal power, the relay closes, and the 
controller or sensor 0-10V lines go to high impedance allowing the load to 
go to full output powered from the EM Source. Commands to change the 
device output from full are ignored when the Emergency Sense Module is 
in this mode. Upon restoration of normal power, the controller or sensor 
will automatically resume normal operation.

Emergency Self-Test: 

NFPA 101 Life Safety Code and NEC (Article 

700.3(B)) requires regular testing of all emergency equipment. To 
perform a test of these products, a Test Switch that is a normally open, 
momentary-break type, that returns the equipment to normal status when 
released can be installed locally to interrupt normal power and perform 
emergency system test. 

* The diagram below depicts a “Momentary-Break Type Test Switch” ($) 
on the normal power line to trigger the emergency systems test. Clarify 
requirements with all local authorities.

Intellect™

EMERGENCY

SENSOR
MODULE

ZL027-0ES

FIXTURE

LIGHT FIXTURE

EMERGENCY

POWER

LIGHTING CIRCUIT

LINE FEED

(NORMAL POWER)

AUX +

AUX -

VIOLET (DIM +)

GRAY (DIM -)

LINE

LINE

NEUTRAL

NEUTRAL

$*

Controller or
Sensor

12 in. C

a

ble

provided
with
Emergency
Sensor Module

A

U

X

+

A

U

X

-

D

I

M

+

D

I

M

-

Neutr

a

l

LN

LN

GND

(-) LED

(-) AUX

(-) DIM

(+) DIM

(+) AUX

(+) LED

1-Channel

LED Driver

With Auxili

a

ry

Power Output

Line

E

a

rth

D

A

L

I

+

D

A

L

I

-

Neutr

a

l

LN

LN

GND

(-) LED

(-) DALI

(+) DALI

(+) LED

DALI

LED Driver

Line

E

a

rth

N

C

N

C

Reset  
Button

WARNINGS

• 

READ AND FOLLOW ALL SAFETY INSTRUCTIONS.

•  

TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER AT CIRCUIT BREAKER OR 
FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.
•  Controller is intended to be installed by the fixture manufacturer, but in some cases may be 

installed in the field. Field installation must use approved electrical enclosures.  

NOTE: 

Suitable for use in air handling spaces (plenums).

•  The use of accessory equipment not recommended by the manufacturer may cause an 

unsafe condition.

•  For indoor applications only. 

DO NOT

 use outdoors.

•  

DO NOT 

use this equipment for other than intended use.

•  

DO NOT

 mount near gas or electric heaters.

•  Equipment should be mounted in locations and at heights where it will not 

be subjected to tampering by unauthorized personnel.

•  Use this device with 

COPPER OR COPPER CLAD WIRE ONLY.

• 

SAVE THESE INSTRUCTIONS.