background image

ENOCEAN CONTROL TRANSMITTER

Power Input:

 100-277 VAC, 50/60 Hz

Cat. No. WSTLT-9D0

DI-001-WSTLT-00B

WARNINGS AND CAUTIONS:

•   

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER

 at circuit breaker or fuse and test that power is off before wiring!

•   To be installed and/or used in accordance with appropriate electrical codes and regulations.
•  If you are unsure about any part of these instructions, consult an electrician.
•  This product is intended only for use indoors and in dry locations.

NOTES:

•  For use with Leviton

®

 LevNet RF™ 902 MHz products.

•   It may be more convenient to link the wireless controls to the Control Transmitter prior to final installation.

DESCRIPTION

Use the Control Transmitter to wirelessly bridge control from one circuit to another. 
The Control Transmitter monitors any line voltage circuit and broadcasts the status 
to wirelessly control one or more circuits connected to compatible receivers. Use the 
Control Transmitter with hardwired switches, occupancy sensors or light sensors to 
extend the controlling capacity of the sensors beyond the wires.

FEATURES

•  

Easy-to-use

 - eliminates switch-leg runs.

•   

Reliable range

 - unique ID of each control transmitter activates only the intended 

receiver(s).

•   

Saves energy

 - conserves energy and saves money by using the control 

transmitter in load shedding or energy-efficient HVAC control applications; 
connects HVAC, lighting, or other devices to a relay receiver to turn them OFF and 
ON automatically in sync with any device connected to a control extender.

•   

Simple wireless control

 - economy HVAC controls, interlocked motor control, and 

secondary circuit follows power status of primary circuit.

•   

Control the way you want it

 - controls one or multiple new devices with an 

existing switch and senses power state of one device, and wirelessly controls a 
receiver connected to another device.

COMPATIBLE DEVICES

•  WSD05-9D0
•  WSD20-9D0
•  WSP20-9D0
•  WSS20-G9N
•  WSS20-N9N
•  WSG15-D9W
•  WSG15-S9W

CERTIFICATIONS

•  ETL:

 UL 60730 (U.S.)

•  ETL:

 CSA c22.2 no.14-05 (Canada)

•  CE:

 IEC 60730

•  ETL:

 UL 2043 (Plenum)

•  IEC

 61000-4-5 (Surge)

•  FCC:

 SZV-STM300U (US)

•  IC:

 5713A-STM300U (Canada)

EQUIPMENT NEEDED FOR INSTALLATION

•  Slotted/Philips Screwdriver
•  Wire Nuts/ Connectors
•  Electrical Tape

CHOOSE THE OPTIMAL MOUNTING LOCATION

The long term reliability and wireless performance of the Relay is strongly influenced by 
the mounting location. Choose a mounting location carefully. For best radio performance:

• Straighten antenna out and away from metal.
•  Create separation distance away from interfering electronics such as fluorescent 

tube ends, electronic transformers/power supplies, motors, etc.

• Avoid mounting inside metal enclosures.
•  Obstructions of metal, concrete and dense building materials will reduce the range. 

Mount higher and away from obstructions to maximize the range.

• Confirm operating environment does not exceed temp. or humidity specifications.
• Site survey tools are available to help fine tune wireless communications.

INSTALLATION

1.  WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER

 at circuit 

breaker or fuse and test that power is off before wiring!

2.  PLAN: 

Identify best mounting locations for receiver and transmitter. Perform 

range test to confirm operation prior to installation.

3.  CONNECT:

 Connect the Control Transmitter to circuit following wiring diagram 

and local electrical codes. Restore power.

4.  LINK:

 Follow Instructions provided with receiver. Press and release MENU button 

to send Link signal.

5. TEST: 

Use the Sensor Link Test Mode (below) to test operation.

LINKING INSTRUCTIONS

Refer to the Receiver installation guide for Linking instructions. Press and release the 
MENU button to send a Link signal during the linking process.

SENSOR LINK TEST MODE

Some receivers support Sensor Link Test Mode. If supported, after Linking, press the 
MENU button on the Control Transmitter 5 times to activate the Sensor Link Test Mode 
in any linked receivers. Subsequent presses of the MENU button will cause receivers 
to toggle: 

1)

 to confirm that the Control Transmitter is linked.

2)

  to test the reliability of wireless communications. 

Receivers will time out of Sensor Link Test Mode after 60 seconds of inactivity.

SPECIFICATIONS

Frequency:

902 MHz

Range:

50-150 feet (typical)

Power Input:

100-277 VAC 50/60 Hz

Power Consumption:

<0.5 W @ 120 VAC

Output:

Wireless Control Signal

Transmit EEP:

A5-3F-01, (default)
MENU button transmits Link Packet

Addressing:

Factory set unique ID
(1 of 4 Billon)

Operating Temp:

+32˚ to +122˚ F (0˚ to +50˚ C)

Storage Temp:

-4˚ to +176˚ F (-20˚ to +80˚ C)

Humidity:

10-95% non-condensing

DIMENSIONS

CONTROL

TRANSMITTER 

1.60”

(34.8 mm)

2.61”

(66.29 mm)

1.73”

(44 mm)

2.1

1”

(54 mm)

1.09”

(27.7 mm)

EEPS:

- A5-3F-01 - Control Extender (default)

English

INSTALLATION

WEB 

VERSION

Отзывы: