Leuze electronic GmbH + Co. KG
MA 238
i
63
16.4 Bar code reader BCL 300i, BCL 500i, BCL 600i (S4 switch position 4)
Specifications for the serial interface
Specifications for Command mode
To activate the Command mode, bit 0 must be set to 1 in control byte 0.
For further information, see chapter 11.1.3 "Command Mode", Figure 11.2.
Recommended settings
• Input data: dependent on the number of digits of the bar code that is to be read.
With an 18-digit bar code (+ 2 bytes of status bytes), for example, it is advisable to use the 24-byte
setting.
• Output data: 8 bytes
Standard Parameter
BCL 300i, BCL 500i, BCL 600i
Baud rate
9600
Data mode
8N1
Handshake
No
Protocol
Framing protocol without acknowledgment
Frame
<STX> <Data> <CR> <LF>
Control bit Meaning
Corresponds to serial
command (ASCII)
0
Version query
v
1
Activation / deactivation reading gate
+ / -
2
Reference code teach-in activation / deactivation
RT+ / RT-
3
4
Autom. configuration of reading task activation / deact.
CA+ / CA-
5
Switching output 1 activation
OA1
6
Switching output 2 activation
OA2
7
Switching output 1 deactivation
OD1
8
Switching output 2 deactivation
OD2
9
10
11
12
13
Parameter - difference to default parameter set
PD20
14
Reset parameters to default values
PC20
15
Device restart
H