Electrical connection
Leuze electronic
CML 730-PS
53
7.2
Connection and interconnection cables
7.3
Device connections
The light curtain is provided with the following connections:
7.4
Digital inputs/outputs on connection X1
Figure 7.4: Digital input/output schematic diagram
7.5
Electrical connection – CML 700i with IO-Link/analog interface
The electrical connection of devices with IO-Link and analog interfaces is established in the same way.
NOTICE
Competent persons and approved purpose!
Only allow competent persons to perform the electrical connection.
Select the functions so that the light curtain can be used as intended (see chapter 2.1).
Device
connection
Type
Function
X1 on receiver M12 connector,
8-pin
Control interface and data interface:
• Voltage supply
• Switching outputs and control inputs
• Configuration interface
X2 on receiver M12 socket,
4-/5-pin
• Synchronization interface (for devices with analog output or
IO-Link interface)
X3 on
transmitter
M12 connector,
5-pin
Synchronization interface (for all controller types)
NOTICE
Single assignment of input functions!
Each input function may only be used one time. If multiple inputs are assigned the same function, mal
-
functions may occur.
X1-1
X1-6/7
GND
18 - 30 VDC
100 mA (max. 250 mA)
X1-3
X1-2/5
10k
10k
X1-3
NOTICE
Light curtain grounding!
Ground the light curtain before establishing an electrical connection or connecting the voltage supply