Starting up the device - Configuration
Leuze electronic
BCL 604i
80
Parameter
Table 10.41:
Parameters for module 62
Parameter length
3 byte
Input data
None
Output data
None
10.11.4Module 63 – Alignment
Description
The module defines input and output data for the alignment mode of the device. The alignment mode is
used for easy alignment of the device with the bar code. Using the transmitted decoding quality as a
percentage, the optimum alignment can be easily selected. This module should not be used in connection
with module 81 (AutoReflAct) as this may cause malfunctions.
Parameter
None
Input data
Table 10.42:
Input data for module 63
Input data length
1 byte
Parameter
Description
Addr.
Data type
Value range
Default
Unit
Language selec
-
tion
Language selection for the display.
A language which was selected via the display
is overwritten by this parameter.
0.0 … 0.2
Bit
1: English
2: German
3: Italian
4: French
5: Spanish
0
-
Display illumina
-
tion
Off after 10 min., or permanently on.
0.3
Bit
0: Off after 10 min.
1: Permanently on
0
-
Display contrast
Contrast setting of the display. The contrast
changes under extreme ambient temperature
and can be adjusted with this parameter.
0.4 … 0.5
Bit
0: Light
1: Medium
2: Strong
1
-
Password protec
-
tion
Password protection on/off
0.7
Bit
0: OFF
1: ON
0
-
Password
Password specification.
Password is only active if password protection
is on.
1 … 2
UNSIGNED16 0000 … 9999
0000
-
This module overwrites the local display settings. Following activation of this module, the lan
-
guage selection, the setting for password protection and the specified password set in this mod
-
ule take effect.
Input data
Description
Addr.
Data type
Value range
Init value Unit
Decoding quality
Transmits the current decoding quality of the
bar code located in the scanning beam
0
Byte
0 … 100
0
Percent
-
age