Description ODSL 30
Leuze electronic GmbH + Co. KG
ODSL 30
39
Setting the offset
Configuration is performed using the membrane keyboard and display:
Applic. Param.
->
Offset/Preset
The following can be entered:
•
Offset Direction
Selection
... positive
or
... negative
, i.e. specifies whether the offset value is added to or
subtracted from the measurement value.
•
Offset value [mm]
Enter the offset value.
The set offset value is subtracted from the calculated (digital) measurement value of the sensor if
nega-
tive
was set for the
Offset Direction
.
Example:
Measurement value of the ODSL 30:
1500mm,
Input:
Offset value: 100mm,
Offset Direction: … negative
Output on the display and at the interface: 1400 mm
Preset presetting
Configuration is performed using the membrane keyboard and display:
Applic. Param.
->
Offset/Preset
Procedure for setting a preset value:
• Enter nominal value ->
Preset value [mm]
• In menu item
Preset calculate
, select the option
... active
• Press the key to confirm.
A measurement is made, the preset is stored and the ODSL 30 is ready.
The offset value is automatically calculated from the measurement value and nominal measurement value
(preset value) and entered as the offset in the configuration. A preset is deactivated by entering an offset
value of zero.
Example:
Input:
Preset value: 1400mm,
Object dist. 1300mm in front of ODSL30: Preset Calculation ...active, trigger
measurement, an offset of +100mm
is automatically stored
Object distance: 1300 mm
Output to display and interface: 1400 mm
Object distance: 1400 mm
Output to display and interface: 1500 mm
ENTER