How to release the TMC 66:
5.12
Operating Conditions without Muting Function
In principle, the test monitoring unit can be used in two operating modes; with and without
muting function.
TMC 66 without muting function, without start- and restart interlock
Waiting mode
In the waiting mode the single beam safety light barrier is free (green LED).
Activation is not used. The safety outputs are open. This state is displayed by the red LED.
The waiting state is displayed through state "11" on the 7-segment display.
Protection mode
In protection mode, the function of the single beam safety light barrier is cyclically tested
every two seconds. The free protective field is displayed by the green LED.
Activation is used (green LED). The safety output is closed which is displayed by a green
LED.
1. Emergency stop of the unit
Disconnect the supply voltage at the
TMC 66
2. Reconnect the supply voltage,
wait for 2 sec. until the unit is ready to operate
3. Activate the muting preparation
Connect a high-potential to the Control 1
and Control 2 inputs
The TMC 66 activates the muting function
internally
4. Press the start-button at the TMC 66
The TMC 66 closes the release circuit
5. Switch the unit on again
The single beam safety light barrier is re-
leased, since the conveyor belt restarts
6. The unit switches back to automatic operation
Fig. 5.12-1:
Waiting mode
Single Beam
Safety Light
Barrier
Start
activation