Diagnostics and troubleshooting
12.1
General causes of errors
12.2
Interface errors
Error
Possible error cause
Measures
Status LED
PWR
Off
• No supply voltage connected to the device
• Hardware error
• Check supply voltage
• Send device to customer service
Red, flashing
• Warning
• Query diagnostic data and carry out the resulting
measures
Red, continuous light
• Error: no function possible
• Internal device error, send in device
Orange, continuous
light
• Device in service mode
• Reset service mode with webConfig tool
Status LED
NET
Off
• No supply voltage connected to the device
• No IP address assigned
• Hardware error
• Check supply voltage
• IP address assigned
• Send device to customer service
Red, flashing
• Communication error
• Check interface
Red, continuous light
• Double IP address
• Check network configuration
Table 12.1:
General causes of errors
Error
Possible error cause
Measures
No communication via USB
service interface
• Incorrect connection cable
• Connected BCL 558
i
is not detected
• Check connection cable
• Install USB driver
Sporadic errors at the
Ethernet interface
• Incorrect wiring
• Effects due to EMC
• Overall network expansion exceeded
• Check wiring:
- In particular, check wire shielding
- Check the cable used
• Check shielding (shield covering in place up to the
clamping point)
• Check grounding concept and connection to functional
earth (FE)
• Avoid EMC coupling caused by power cables laid parallel
to device lines
• Check max. network expansion as a function of the max.
cable lengths
Table 12.2:
Interface error