Commissioning and configuration
120
BCL 548
i
Leuze electronic
You can find the GSD file for the respective device model at
www.leuze.com
.
All data in modules required for operating the
BCL 548
i
is described in this file. These are
input and output data and device parameters for the functioning of the
BCL 548
i
and the
definition of the control and status bits.
If parameters are changed, e.g., in the project tool, these changes are stored on the PLC
side in the project, not in the GSD file. The GSD file is a certified and integral part of the
device and must not be changed manually. The file is not changed by the system either.
The functionality of the
BCL 548
i
is defined via GSD parameter sets. The parameters and
their functions are structured in the GSD file using module. A user-specific configuration
tool is used during PLC program creation to integrate the required modules and configure
them appropriately for their respective use. During operation of the
BCL 548
i
on the
PROFINET-IO, all parameters are set to default values. If these parameters are not changed
by the user, the device functions with the default settings delivered by Leuze electronic.
For the default settings of the
BCL 548
i
, please refer to the following module descriptions.
10.4.3
Step 3 – Hardware configuration of the S7 PLC: Configuration
For the configuration of the PROFINET-IO system using the HW Config of the SIMATIC
Manager, insert the BCL 548
i
into your project. An IP address is now assigned to a unique
"device name".
Table 10.1:
Assignment of the device names to IP addresses