Display and control panel
Leuze electronic
BCL 504
i
93
TNT 35/7-24V
8.4
Operation
Shown here is an example describing important operating procedures in detail.
Parameter enabling
During normal operation parameters can only be viewed. If parameters need to be changed,
the
ON
menu item in the
Parameter enabling
menu must be activated. To do this proceed
as follows:
Attention!
The BCL 504
i
is deactivated on the PROFIBUS if parameter enabling is activated via the
display. The device is reactivated on the PROFIBUS after parameter enabling is exited.
Notice!
In the PROFIBUS network, configuration is performed exclusively via the PROFIBUS.
Parameters set via the display when operating the BCL 504
i
on the PROFIBUS are over-
written by the parameters set in the GSD modules. For GSD modules which are not actively
used on the PROFIBUS, the default settings of the barcode reader apply, see "Overview of
the project modules" on page 112. Thus, the PROFIBUS presets values to all parameters.
Parameter 1
Parameter handling
Decoder table
Digital SWIO
PROFIBUS
In the parameter menu, use the
buttons to select the
Parameter handling
menu item.
Press the enter button to enter the
Parameter handling
menu.
Parameter handling 1.1
o Parameter enabling
Parameters to default
In the Parameter handling menu, use the
buttons to
select the
Parameter enabling
menu item.
Press the enter button to enter the
Parameter enabling
menu.
Parameter enabling
OFF
o ON
Standard ----- Unit
OFF | |
In the Parameter enabling menu, use the
buttons to
select the
ON
menu item.
Press the enter button to switch on parameter enabling.
Parameter enabling
OFF
O ON
Standard ----- Unit
OFF | |
The PWR LED lights up red. You can now set individual
parameters via the display.
Press the ESC button twice to return to the main menu.
ESC
ESC