Fast commissioning / operating principle
Leuze electronic
BCL 504
i
19
TNT 35/7-24V
After saving the PROFIBUS address, the BCL 504
i
performs a restart and then returns to
operation with the barcode reading menu.
Notice!
Permissible values for the PROFIBUS address are 0 … 125. Make certain that a different
PROFIBUS address is assigned to each PROFIBUS participant.
All other parameters required for the reading task, such as setting the code type and number
of digits, etc., are set using the engineering tool of the PLC with the aid of the various avail-
able modules (see chapter 10.4).
3.5
BCL 504
i
on the PROFIBUS
ª
Install the GSD file associated with the BCL 504
i
in the PROFIBUSmanager of your con-
trol.
ª
Activate the desired modules (at least module 10 and one of the modules 21 … 27).
ª
Store the slave address for the BCL 504
i
in the PROFIBUSmanager. Ensure that the
address is the same as the address configured in the device.
You can find further information beginning on page 106.
In the upper right part of this display, you can check the
address which you set.
31