Diagnostics and troubleshooting
Leuze electronic
BCL 600i/BCL 601i
72
13
Diagnostics and troubleshooting
13.1 General causes of errors
Table 13.1:
General causes of errors
13.2 Interface errors
Table 13.2:
Interface error
Error
Possible error causes
Measures
Status LED PWR
Off
• No supply voltage connected to the device
• Check supply voltage
• Hardware error
• Send device to customer service
Red, flashing
• Warning
• Query diagnostic data and carry out the
resulting measures
Red, continuous light
• Error: no function possible
• Internal device error, send in device
Orange, continuous light
• Device in service mode
• Reset service mode with webConfig tool
or display
Status LED NET
Off
• No supply voltage connected to the device
• Check supply voltage
• Hardware error
• Send device to customer service
Red, flashing
• Communication error
• With slave: network error
• With master: network error following initial
-
ization
• Check interface
• Check interface, addressing and el.
connection of the slave
• Check interface, addressing and el.
connection of the slave
Red, continuous light
• No communication
• Incorrect wiring
• Incorrect address
• Check interface
• Check wiring
• Check addressing
Orange, flashing
• Timeout -> Error on interface
• Check interface wiring
Error
Possible error causes
Measures
No communication via USB service interface
• Incorrect interconnection cable
• Connected device is not recognized
• Check interconnection cable
• Install USB driver
No communication via
RS 232 / RS 422/ RS 485
• Incorrect wiring
• Check wiring
• Different baud rates
• Check baud rate
• Different protocol settings
• Check protocol settings
Sporadic errors on the
RS 232 / RS 422 / RS 485 interface
• Incorrect wiring
• Check wiring
• In particular, check wire shielding
• Check the cable used
• Effects due to EMC
• Check shielding (shield covering in place
up to the clamping point)
• Check grounding concept and connection
to functional earth (FE)
• Avoid EMC coupling caused by power
cables laid parallel to device lines
• Overall network expansion exceeded
• Check max. network expansion as a func
-
tion of the max. cable lengths