Leonard TMS-25 Скачать руководство пользователя страница 1

BULLETIN G-2B-TMS 

August, 2018

1360 Elmwood Avenue, Cranston, RI 02910 USA

Phone: 401.461.1200 Fax: 401.941.5310

Email: 

[email protected]

Web Site: http://www.leonardvalve.com

INSTALLATION ADJUSTMENT SERVICE

THERMOSTATIC STEAM AND WATER MIXING VALVE

TYPE TMS-25, 50, 80, 125, 150 

IMPORTANT! Provide valve serial number (stamped on cover of valve) when ordering parts!!

INSTALLATION

COLD INLET

STEAM INLET

H

C

THERMOSTATIC

LEONARD

OUTLET

1. Valve should be installed at a location where it can easily be

cleaned, adjusted or repaired.

2. The inlets are clearly marked on the valve body casting.

Connect the Steam into the inlet marked “H” cold water into
the inlet marked “C”.

3. Use pipe cement sparingly. Supply pipes should be flushed

before the valve is connected. Flush outlet pipe and valve as
soon as it is connected.

4. Union Angle stops furnished must be installed on both supply

lines as shown above.

5. A shutoff valve must be installed on the outlet pipe. Type

TMS valves do not have a built in shutoff.

6. IMPORTANT! Not for use with steam and water pressures

above 80 PSI (5.5 bar). The prevailing steam (or hot water)
pressure must be slightly lower than the cold water pressure.

7.

Not for use with unequal pressures. Install pressure reducing

valves where unequal pressure conditions exist.

8. Maximum recommended operating temperature of 200°F

(93°C). Note This maximum temperature is for valve only,
see hose specification for rating temperature.

9. Provide a steam trap prior to the blender to eliminate water

hammer.

10. When used for high temperature wash down (140°F to

180°C) operators should wear protective gloves, boots and
clothing, and they should be given safety instructions in the
proper use of high temperature hot water.

CAUTION:

These valves may pass live steam under certain circumstances. A limit stop is

simply a mechanical setting to prevent excessive handle rotation. When turned to full HOT
valve may deliver water in excess of safe temperatures, therefore the limit stop MUST BE
RESET BY THE INSTALLER. Protective clothing must be worn at all times.

!

WARNING:

This

product

can

expose

you

to

chemicals including lead, which is known to the State
of California to cause cancer. For more information, go
to

www.P65Warnings.Ca.gov

Содержание TMS-25

Страница 1: ...or use with steam and water pressures above 80 PSI 5 5 bar The prevailing steam or hot water pressure must be slightly lower than the cold water pressure 7 Not for use with unequal pressures Install p...

Страница 2: ...W SNAP CAP THERMOSTATIC LEONARD C H TMS 25 TMS 50 80 TMS 125 150 PACKING GASKETS PORT SLEEVE ASSEMBLY THERMOSTAT GROUP CHECKSTOPS 1 Leak at pointer rod 2 Leak between valve cover and base 3 Valve deli...

Страница 3: ...an with a NON CORROSIVE CLEANING AGENT AND SOFT CLOTH DO NOT USE ABRASIVES then wash parts thoroughly wipe with a dry cloth and re assemble The PORT SLEEVE should be assembled with the SHOULDER to the...

Страница 4: ...OINTER SET SCREW TM 36 REMEMBER THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS SEE MAINTENANCE GUIDE AND RECORD MGR 1000 NOTE AFTER INSTALLING NEW PARTS IT WILL BE NE...

Страница 5: ...TER ROD TM 28A TM 16A 125 PLATE DIAL LEONARD THERMOSTATIC C H TM 8 TGM 2 125 THERMOSTAT GROUP STUD COIL SLEEVE TM 15B 125 RF TM 25D COVER STOP 5236 O RING KIT R 125ST REBUILDING KIT 03 ST LOWER STEM P...

Страница 6: ...11 C 22 C 33 C 94 5 83 5 25 0 22 0 60 0 69 0 53 5 15 5 18 0 14 0 20 F 30 F 50 F 40 F 60 F 38 C 44 C 48 0 45 5 12 5 12 0 70 F 80 F l min GPM l min GPM GPM l min GPM l min TEMPERATURE RISE FLOW RATE GPM...

Страница 7: ...r labor or incidental or consequential damages Any alteration or improper installation or use of the product will void this limited warranty TEMPERATURE RISE 265 75 5 38 0 10 0 0 0 227 189 151 114 20...