INSTALLATION ADJUSTMENT SERVICE

HIGH CAPACITY MANIFOLD SYSTEM

TM-186-30015050-PRV

IMPORTANT! Provide valve serial numbers (stamped on cover of valves) when ordering parts!!

D

D

C

O

D

L

R

I

P

A

E

L

E

T

N

O

M

O

T

H

T

S

R

M

R O

WA

H

T

E

T

A

I C

56"

64"

HOT

INLET

COLD

INLET

OUTLET

CIRCULATION
CONNECTION

APPROX.

INSTALLATION

1. Type TM manifold systems are factory pre-

assembled and tested and include large and

small thermostatic water mixing valves which

function as a system to meet both high and low

demand for tempered water.

2. System should be installed at a location where it

can easily be cleaned, adjusted or repaired.

3. System supplies must be connected as shown

(Hot-left, Cold-right). Exercise caution when

soldering.

4.

Flush pipes thoroughly after system has been

connected.

5.

If this assembly is installed on a recirculated

hot water system it

MUST

be piped according

to a

REQUIRED PIPING METHOD

(see

page 4).

6.

Refer to page 3 of this bulletin for correct Setup

Instructions.

Maximum Operating Pressure 125 PSI (8.6 BAR) 

CAUTION

All thermostatic water mixing valves have limitations. They will not provide the desired accuracy outside of their flow
capacity range. Consult the capacity chart on page 9. Minimum flow must be no less than as shown.

REMEMBER! THIS IS A CONTROL SYSTEM WHICH MUST BE CLEANED AND MAINTAINED ON A 
REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD MGR-1000).

WARNING:

This

product

can

expose

you

to

chemicals including lead, which is known to the State
of California to cause cancer. For more information, go
to

www.P65Warnings.Ca.gov

!

Содержание TM-186-30015050-PRV

Страница 1: ...cleaned adjusted or repaired 3 System supplies must be connected as shown Hot left Cold right Exercise caution when soldering 4 Flush pipes thoroughly after system has been connected 5 If this assembl...

Страница 2: ...e of the WEB which is cast on the RIGHT side of the cover 4 The new maximum temperature has now been set Test this temperature by holding a thermometer under the flow of water to be certain it is as d...

Страница 3: ...50 GPM 7 Set outlet temperature of mixing valve A to the safe required level read temperature on gauge T1 8 Turn off enough fixtures to flow 25 GPM downstream of the assembly 9 Carefully adjust screw...

Страница 4: ...tem Pressure reducing pilot 3 not serviceable REMEDY Check create inlet pressure Create demand flow Turn adjusting screw on pressure reducing pilot 3 clockwise Bleed air from cover and bleed air from...

Страница 5: ...WATER DOMESTIC TEMPERED THERMOMETER SETUP OPTIONAL BALL VALVE FOR CHECK AQUASTAT T WITH CHECK VALVE 1 MAKE SURE NO WATER IS BEING DRAWN IN THE BUILDING OPEN BALANCING VALVE 1 APPROXIMATELY HALF WAY A...

Страница 6: ...d thimble may then be lifted out There is no shoulder for the TM 150 Port Sleeve 5 Clean with a non corrosive cleaning solution DO NOT USE ABRASIVES The port sleeve should be reassembled in the valve...

Страница 7: ...LARGE TM VALVE PARTS REPAIR KITS GLAND PKG KIT R 300 REBUILDING KIT 3 3A 300 NUT ASSY PORT SLEEVE COIL SLEEVE 8 300 STUD FLANGE TG 4 300 GROUP ASSY TGM 1 300 PORT SLEEVE POINTER ROD THERMOSTAT TG 2 30...

Страница 8: ...TM 50 SWIVEL NUT 013 SCREEN 014 BONNET 03 LOWER STEM PACKING 011 BODY O RING UPPER STEM 010 PACKING 05 SWIVEL 09 50 RF TM 50 09 125 RF TM 150 LOCK TYPE POINTER TM valves are furnished with lockable p...

Страница 9: ...re no warranties express or implied which extend beyond the description contained herein There are no implied warranties of merchantability or of fitness for a particular purpose In no event will Leon...

Отзывы: