LMS Overview 

 

Buttons: 

TEST

/

RESET

,   

STEP

   DOWN

,   

UP

,   

MUTE

/

MENU

  

 

Runtime Display

 

 

1:   8.9'C

 

  

2:   8.4'C

 

 

Edit Parameters

 

At Runtime tap

 MENU

 

Repeat

 MENU

,

 MENU

,.. To

 Edit Limits

 , 

 Edit Times

 , 

Return to Runtime

 

Edit Limits

 

or while in Edit tap

 MENU

 AND 

RESET

 simultaneously to access 

*SETUP*

 group

 

1 Low 
     -30.3

  

To step through parameters in group use 

STEP

 

To STEP BACK tap TEST

 

To modify parameter values use 

DOWN

 , 

UP

 

 

To step out of edit and back to runtime screen use 

MENU

 

Group 1

 Limits 

 1 Low, 1 High, 2 Low, 2 High

 

Group 2

 Times 

 1AlarmDelay, 2AlarmDelay, DoorAlrmDly, 
 1RelayDelay, 2RelayDelay, Mute

 

Special Group

 *SETUP* 

 1 Offset, 2 Offset, 
 # channels, 
 1 Define,

 

0:tenthC 1:wholeC 2:tenthF 3:wholeF 4:wholeRH

 

 2 Define, 
 Relay Def,

 

0:single unit relay 1:individual channel relays

 

 DoorAlarm

 

-1:AlarmOnContactClosed 0:NoAlarm 1:AlarmOnContactOpen

 

 Unit ID

 

-1:AlarmOnContactClosed 0:NoAlarm 1:AlarmOnContactOpen

 

 IP1, IP2, IP3, IP4, 

IP 1.2.3.4

 

 NetworkCode  

 

-30,000 to 30,000  

Setup Web Page Password

 

 

Door Status Display 

Upon Door Alarm, the Door Status Displays until user responds, OR  By User command at 
Runtime tap

 STEP

 

Door 

Door 

Door 

 Closed 

 Open 

 Open 

<DoorStatus: 

Open/Closed>

 

 Ok 

 Delay 

 Alarm

 

<AlarmStatus: 

Ok/Delay/Alarm>

 

 

Low/High Alarm Setpoint Display 

At Runtime tap

 DOWN

 

AlarmLow 

2.0’C 

AlarmHigh  8.0’C 

AlarmLow 

2.0’C 

AlarmHigh  8.0’C 

 
 
 

 

 

 

Содержание LMS-188-4P

Страница 1: ...d Avenue Cranston RI 02910 Tel 401 461 1200 Fax 401 941 5310 Toll free 800 222 1208 www leonardvalve com G LMS 188 4P February 2021 WARNING This product can expose you to chemicals including lead whic...

Страница 2: ...time Display Error Bookmark not defined Alarm Conditions Error Bookmark not defined Temperature Alarms 5 Low High Alarm Limits 5 Min Max Readings 5 LMS Email Notification Feature 6 LMS Overview 10 RDU...

Страница 3: ...tep button STEP o Alarm Limits decrement button vv o Min Max increment button o Mute Menu increment button MUTE MENU Sensor Probe The probes supplied with the Multi Probe Alarm System are highly accur...

Страница 4: ...t finger tight Warning do not overtighten Power up Shows LMS startup screen NO BATTERY Power Down Install Battery The unit will run without a backup battery but will show NoBatt on the display to indi...

Страница 5: ...elay Delay times Units with a single relay have one Relay Delay time that applies to any alarm condition Limit Parameters 1 Low 1 High 2 Low 2 High 3 Low 3 High 4 Low 4 High Time Parameters 1AlarmDela...

Страница 6: ...to 30000 22718 Depending on the Network being utilized the factory setting on the alarm unit for IP1 IP2 and IP3 may need to be changed to match the corresponding settings of the network IP4 may also...

Страница 7: ...r through Control Panel or the internet connection icon on your taskbar 2 Click on Local Area Connection to bring up the status page 3 Click properties and then highlight Internet Protocol Version 4 T...

Страница 8: ...is utilized See Network administrator for DNS Server SMTP information If these parameters are unavailable use 8 8 8 8 for DNS Server smtp 1and1 com for SMTP Server t140 hampshirecontrols com for SMTP...

Страница 9: ...IP address to access the unit After reviewing main web page add setup html to the IP to access the Setup Info Name setupadmin unchangable case sensitive Passcode 22718 Enter your Subnet Mask Gateway D...

Страница 10: ...RelayDelay 2RelayDelay Mute Special Group SETUP 1 Offset 2 Offset channels 1 Define 0 tenthC 1 wholeC 2 tenthF 3 wholeF 4 wholeRH 2 Define Relay Def 0 single unit relay 1 individual channel relays Doo...

Страница 11: ...while still providing the degree of safety required III Installation 1 Remove the plastic case cover by removing the 2 Phillips screws from the back Apply light pressure on the face plate the cover a...

Страница 12: ...that an alarm condition has persisted for the set time and has been transmitted to the monitoring device this LED will continue to flash even if the alarm condition has corrected itself Pressing RESET...

Страница 13: ...quires a dedicated 110 VAC outlet to plug into See wiring diagram below for reference Do Not Energize SCO LMS 188 4P or solenoid valve until wiring is complete Solenoid valve and associated power supp...

Страница 14: ...arm is active the relay on the LMS 188 4P will switch to N C and the solenoid will shut down Solenoid valve and associated power supply are to be provided by others Installation Solenoid power supply...

Страница 15: ...LMS Operating Manual Page 15...

Отзывы: